19XR PIC 6 CONF_MS MASTER SLAVE TABLE CONFIGURATION SHEET
19XR PIC 6 CONNECT - BMS PROTOCOL TABLE CONFIGURATION SHEET
DESCRIPTION RANGE UNITS DEFAULT VALUE
Slave Address 1 to 236 2
Master/Slave Select
0 = Disable
1 = Master
2 = Slave
0 to 2 0
Chiller Connection Type
0 = Parallel
1 = Series
0 to 1 0
Middle Sensor Option YES/NO YES
Master Lead Lag Select 0 to 1 0
Series Counter Flow NO/YES NO
Master per Capacity 25 to 75 % 50
Lag Shutdown Threshold 25 to 75 % 50
Prestart Fault Timer 2 to 30 min 5
Lead Unload Threshold 50 to 100 % 100
Lead/Lag Balance Delta 40 to 400 hr 168
Lag Start Timer 2 to 30 min 10
Lag Stop Timer 2 to 30 min 10
Lead Pulldown Time 0 to 60 min 0
Lag Minimum Running Time 0 to 150 min 0
Lag Run Delta T 0 to 10.0 ^F 3.0
Lag Off Delta T 0 to 10.0 ^F 1.8
DESCRIPTION RANGE UNITS DEFAULT VALUE
Modbus Configuration
Port J8 Option
0=None, 1=BACnet MS/TP,
2=Modbus RTU
0 to 2 0
Modbus TCP Enable DSABLE/ENABLE DSABLE
Modbus TCP Port Number 0 to 1024 502
Modbus Server UID NO/YES NO
Modbus Metric Unit 0 to 1024 502
Modbus RTU Parity Option
0=No, 1=Odd, 2=Even, 3=Low, 4=High
0 to 4 0
Modbus RTU Stop Bit
1= 1 Bit, 2= 2 Bits
0 to 2 2
Modbus RTU Baudrate
0=9600, 1=19200, 2=38400
0 to 2 0
Modbus Litte Endian NO/YES NO
Modbus Real Type NO/YES NO
BACnet Configuration
BACnet/IP Enable DSABLE/ENABLE ENABLE
BACnet Metric Unit NO/YES YES
BACnet Network 1 to 9999 1600
BACnet Identifier 0 to 9999999 1600001
BACnet Schedule Enable DISABLE/ENABLE DISABLE
MS/TP Mac address 1 to 127 1
MS/TP Baud rate
0=9600, 1=19200, 2=38400, 3=57600, 4=76800,
5=115200
0 to 5 2
MS/TP Max Master 0 to 127 3
MS/TP Max Info Frames 1 to 255 5