CL-10
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - - - - -
CUT ALONG DOTTED LINE CUT ALONG DOTTED LINE
19XR PIC 6 CFGSURGE SURGE CORRECTION CONFIG TABLE CONFIGURATION SHEET
19XR PIC 6 CTRL_ID CONTROL IDENTIFICATION TABLE CONFIGURATION SHEET
19XR PIC 6 LQBP - LOW LOAD CONTROL IDENTIFICATION TABLE CONFIGURATION SHEET
DESCRIPTION RANGE UNITS DEFAULT VALUE
Surge Line Configuration
0=PR, 1=Delta T
0 to 1 0
IGV1 Pos Configuration
0-Degree, 1=Percentage
0 to 1 0
Surge Delta Tsmax 0.0 to 150.0 °F 70.0
Surge Delta Tsmin 0.0 to 150.0 °F 45.0
PR at Full Load Opening 1.0000 to 5.0000 3.0000
PR at Min. Opening 1.0000 to 5.0000 1.5000
IGV1 Full Load Open Deg 90 to 120.0 degree 88.0
Sound Ctrl IGV1 Open Deg 10.0 to 40.0 degree 27.0
IGV1 Minimum Open Deg 0.0 to 10.0 degree 2.0
IGV1 Actuator Max Deg 90.0 to120.0 degree 109.0
Surge Line Offset 1.0 to 3.0 °F 2.0
Surge Line Lower Deadband 0.5 to 3.0 °F 1.5
Surge Line Upper Deadband 0.1 to 3.0 °F 1.5
Surge Line Shape Factor –1.000 to 0.000 –0.010
Sound Line Shape Factor 0.000 to 1.000 0.010
Surge Line Speed Factor 0.00 to 3.00 2.00
Surge Delay Time 0 to 120 sec 15
Surge Time Period 7 to 10 min 8
Surge Delta Amps % 5 to 40 % 20
Rampdown Factor 0 to 1 10 0
GV1 Close Step Surge 1.0 to 3.0 % 2.0
VFD Speed Step Surge 1.0 to 5.0 % 1.5
EC Valve Step Surge 1.0 to 10.0 % 4.0
Surge Profile Step 0 to 2 ^F 1
Surge Profile Offset 0.0 to 5.0 ^F 0.0
High Efficiency Mode DSABLE/ENABLE DSABLE
GV Jumpover Option DSABLE/ENABLE DSABLE
DESCRIPTION RANGE UNITS DEFAULT VALUE
CCN Element Number 0 to 239 1
CCN Bus Number 0 to 239 0
CCN Baud Rate 9600, 19200, 38400 9600
Device Description — 19XRPIC6
Location Description (User-defined
24-digit character string)
Software Part Number:
SCG-SR-2-20S200200
Serial Number =
DESCRIPTION RANGE UNITS DEFAULT VALUE
ECO LBP VLV Option DSABLE/ENABLE DSABLE
ECO LBP VLV Limit 0 to 100 % 100
DSH Deadband for LBP 0 to 20 ^F 2
ECO LBP VLV EVap Appro 1 to 20 ^F 5
Dynamic Demand Limit DSABLE/ENABLE min DSABLE
Ignore DDL Time 0 to 60 30
LCW at Selection Point 32 to 86 °F 45
LCDW at Selection Point 59
to 113 °F 95
100% Lift Demand Limit 10 to 100 % 100
Middle Lift Percent 40 to 80 % 60
Middle Lift Demand Limit 0 to 100 % 80
20% Lift Demand Limit 0 to 100 % 45
LCW at Selection Point 32 to 86 °F 45
LCDW at Selection Point 59 to 113 °F 95