46
APPENDIX A PIC6 SCREEN AND TABLE STRUCTURE (cont)
LEGEND
LEGEND
Control Algo
CCN TABLE NAME: CONTROL
PIC6 PATH: Main Menu Control Algo Menu
MENU NAME MENU TEXT DESCRIPTION ACCESS MENU ICONS
1 CIRACTL Circuit A Control Menu USER
2 CAPCTL Capacity Control USER
3 EPMPCTL Evap Pump Control USER
4 CPMPCTL Cond Pump Control USER
5 OILVCTL Oil Viscosity Control USER
6 HDPRCTL Head Pressure Control USER
Set Points
CCN TABLE NAME: SETPOINT
PIC6 PATH: Main Menu Set Points
LINE PIC6 DESCRIPTION CCN NAME RANGE DEFAULT VALUE
a
NOTE(S):
a. Default value is shown only if configurable.
UNIT READ/WRITE
1
Cooling LCW Setpoint lcw_sp 10 to 120 45 °F RW
2
Ice Build Setpoint ice_sp 15 to 60 40 °F RW
3
EWT Control Option EWT_OPT DSABLE_ENABLE 0 RW
4
Cooling ECW Setpoint ecw_sp 15 to 120 60 °F RW
5
Base Demand Limit dem_base 25 to 100 100 % RW
6
Recycle Shutdown Offset rcyc_lo 0 to 10 5 °F RW
7
Recycle Startup Offset rcyc_hi 0 to 10 5 °F RW
RW Read/Write
General Configuration
CCN TABLE NAME: GENCONF
PIC6 PATH: Main Menu Config Menu General Config
LINE PIC6 DESCRIPTION CCN NAME RANGE DEFAULT VALUE
a
NOTE(S):
a. Default value is shown only if configurable.
UNIT READ/WRITE
1
Ramp Loading Type
Temp=0, Amps=1, Kw=2
rampsel 0 to 2 0 RW
2 Enable Ramp Loading ramp_en DSABLE_ENABLE RW
3 Ramp Rate (per Min) rrate_t 0.5 to 32 0.5 °F RW
4 Ramp Rate (per Min) rrate_a 0.5 to 100 0.5 A RW
5 Ramp Rate (per Min) rrate_k 0.5 to 100 0.5 kW RW
6 Ice Mode Enable ice_cnfg DSABLE_ENABLE RW
7 Ice Mode Recycle ice_rec DSABLE_ENABLE RW
8 Refrigerant Leak Option leak_en DSABLE_ENABLE RW
9 Circuit A Capacity Limit caplim_a 20 to 100 100 % RW
10
Demand Limit Source
0=Local, 1=AnalogIO
dem_sel 0 to 1 0 RW
RW Read/Write