APPENDIX A PIC6 SCREEN AND TABLE STRUCTURE (cont)
LEGEND
Reset Configuration
CCN TABLE NAME: RESETCFG
PIC6 PATH: Main Menu Configuration Menu Reset Config
LINE PIC6 DESCRIPTION CCN NAME RANGE DEFAULT VALUE
a
NOTE(S):
a. Default value is shown only if configurable.
UNIT READ/WRITE
1
Temp Reset Type
None=0, 4-20mA=1, Remote Temp=2,Water DT=3
res_sel 0 to 3 0 RW
2 Degrees Reset at 20mA der_20ma –30 to 30 10.0 ^F RW
3 Maximum Deg Temp Reset deg_rset –30 to 30 10.0 ^F RW
4 Remote Temp Full Reset remtm_fu –40 to 245 65.0 °F RW
5 Remote Temp No Reset remtm_no –40 to 245 85.0 °F RW
6 Deg Reset Water DT Full drwdt_fu –30 to 30 10.0 ^F RW
7 Controlled DT Full Reset ctldt_fu 0 to 15 0 ^F RW
8 Controlled DT No Reset ctldt_no 0 to 15 10 ^F RW
Service Configuration
CCN TABLE NAME: SERVICE
PIC6 PATH: Main Menu Configuration Menu
Service Config CFG
LINE PIC6 DESCRIPTION CCN NAME RANGE DEFAULT VALUE
a
NOTE(S):
a. Default value is shown only if configurable.
UNIT READ/WRITE
1
Evaporator Fluid Type
0=Water, 1=Med Brine, 3=Low Brine
flui_typ 0 to 2 0 RW
2 Brine Freeze Setpoint freezesp –20 to 34 34 °F RW
3 Comp Min Off Time min_off 60 to 1200 120 sec RW
4 Demand Limit At 20 mA dem_20ma 10 to 100 40 % RW
5 Minimum Fluid Temp min_lwt –20 to 38 38 °F RW
6 Maximum Fluid Temp max_lwt 38 to 153 95 °F RW
7 Service Password ser_pass NO_YES RW
8 Service Lockout lockout NO_YES RW
9
Restart Options
0=None, 1=Auto, 2=Swift Restart
rstrtopt 0 to 2 0 RW
10 Starts Limit Bypass stlim_by NO_YES RW
11 Starts Per Period Lim stpperlA 0 to 0 8 RW
12 Comp Start Period cmpstA 0 to 0 3800 RW
13 Starts Per Period Lim stpperlB 0 to 0 8 RW
14 Comp Start Period cmpstB 0 to 0 3800 RW
15 Reset Service Runtime rsthrsvc NO_YES RW
16 Soft Stop Enable sftst_en DSABLE_ENABLE RW
17 Soft Stop Threshold sftst_th 0 to 100 50 % RW
18 Emergency Stop Enable emstopen DSABLE_ENABLE RW
19 Spare Safety Enable spstopen DSABLE_ENABLE RW
20 Powerloss Autoreset Lim pwaulim 4 to 168 168 hours RW
Factory Configuration
CCN TABLE NAME: FACTORY
PIC6 PATH: Menu Config Menu Factory Config
LINE PIC6 DESCRIPTION CCN NAME RANGE DEFAULT VALUE
a
NOTE(S):
a. Default value is shown only if configurable.
UNIT READ/WRITE
1
Refrigerant Type
4=R-134a, 11=R-513A
refrig 0 to 15 4 RW
2 Chiller Tons tons 100 to 600 100 TONS RW
3 HGBP Control Option
hgbp_opt DSABLE_ENABLE RW
4 Design Input kW din_kw 0 to 0 0 kW RW
5 Design Input kW/Ton dkw_ton 0 to 0 0 kW RW
6 Design Ent Evap Temp dewt 0 to 0 0 °F RW
7 Design Lvg Evap Temp dlwt 0 to 0 0 °F RW
8 Design Evap GPM degpm 0 to 0 0 GPM RW
9 Design Evap Press Drop depdft 0 to 0 0 Feet RW
10 Design Evap Refrig Temp dert 0 to 0 0 °F RW
11 Design Ent Cond Temp decwt 0 to 0 0 °F RW
12 Design Lvg Cond Temp dlcwt 0 to 0 0 °F RW
13 Design Cond GPM dcgpm 0 to 0 0 GPM RW
14 Design Cond Press Drop dcpdft 0 to 0 0 Feet RW
15 Design Cond Refrig Temp dcrt 0 to 0 0 °F RW