70
0x0028 40 1 GENUNIT_STATUS Unit Status UINT HR 0 16 0
MV: 0=OFF,
1=DELAY, 2=READY,
3=RECYCLE,
4=PRESTART,
5=STARTUP,
6=AUTORESTART,
7=RUNNING,
8=DEMAND,
9=RAMPING,
10=STOPPING,
11=TRIPOUT,
12=SERV_TEST,
13=PUMPDOWN,
14=LOCKOUT,
15=RESET,
16=LAB_TEST
0x002A 42 2 GENUNIT_min_left Time Until Start FLOAT HR min 0 0 0
0x002B 43 2 GENUNIT_min_run Minimum Runtime Timer FLOAT HR min 0 0 0
0x002C 44 1 GENUNIT_BAC_OCC BACnet Occupied UINT HR 0 1 0
0x002D 45 1 GENUNIT_ONOFFSVC Unit Mode UINT HR 0 3 0
MV: 0=Disabled,
1=Enabled, 2=Serv
Strt, 3=Serv Tst
0x002E 46 1 GENUNIT_LCL_S_S HMI Start/Stop Cmd UINT HR 0 1 0
0x002F 47 1 GENUNIT_CHIL_S_S Cmd Start/Stop UINT HR 0 1 0
0x0030 48 2 GENUNIT_CTRL_PNT Control Point FLOAT HR
°F –4 153 0
°C –20 67.22 –17.78
0x0031 49 1 GENUNIT_EMSTOP Emergency Stop UINT HR 0 1 0
0x0032 50 1 GENUNIT_DEM_LIM Active Demand Limit UINT HR % 0 100 0
0x0033 51 1 GENUNIT_LAG_LIM Lag Demand Limit UINT HR % 0 100 0
0x0034 52 1 GENUNIT_LOC_OCC Local Sched Occupied UINT HR 0 1 0
0x0035 53 1 GENUNIT_ICE_OCC Ice Build Occupied UINT HR 0 1 0
0x0036 54 1 GENUNIT_SYS_STAT System State UINT HR 0 3 0
MV: 0=Off, 1=Delay,
2=On, 3=Tripout
0x0038 56 1 GENUNIT_rpdrstst Swift Restart State UINT HR 0 3 0
MV: 0=Disabled,
1=Enabled, 2=Active,
3=Complete
0x0039 57 1 GENUNIT_ramp_act Ramp Loading Active UINT HR 0 1 0
0x003A 58 2 GENUNIT_ramprate Ramp Rate (per Min) FLOAT HR 0
0x003B 59 2 TEMP_ECW Ent Chill Water Temp FLOAT IR
°F 0
°C –17.78
0x003C 60 2 TEMP_LCW Leaving Chill Water Temp FLOAT IR
°F 0
°C –17.78
0x003D 61 2 TEMP_ECDW Entering Cond Water Temp FLOAT IR
°F 0
°C –17.78
0x003E 62 2 TEMP_LCDW Leaving Cond Water Temp FLOAT IR
°F 0
°C –17.78
0x003F 63 2 TEMP_R_RESET Remote Reset Temp FLOAT IR
°F 0
°C –17.78
0x0040 64 2 TEMP_CTL_FLUI Control Fluid Temp FLOAT IR
°F 0
°C –17.78
0x0041 65 2 TEMP_EVAP_T_A Evap Rfrg Liq Temp A FLOAT IR
°F 0
°C –17.78
0x0042 66 2 TEMP_EVP_ST_A Evap Saturated Temp A FLOAT IR
°F 0
°C –17.78
0x0043 67 2 TEMP_EVPAPP_A Evaporator Approach A FLOAT IR
^F 0
^C 0
0x0044 68 2 TEMP_SUCT_T_A Suction Temperature A FLOAT IR
°F 0
°C –17.78
0x0045 69 2 TEMP_ROT_T_A Rotor Inlet Temp A FLOAT IR
°F 0
°C –17.78
0x0046 70 2 TEMP_SST_A Suct Saturated Temp A FLOAT IR
°F 0
°C –17.78
0x0047 71 2 TEMP_SSH_A Suction Superheat A FLOAT IR
^F 0
^C 0
0x0048 72 2 TEMP_DGT_A Discharge Gas Temp A FLOAT IR
°F 0
°C –17.78
0x0049 73 2 TEMP_DIS_ST_A Discharge Sat Temp A FLOAT IR
°F 0
°C –17.78
0x004A 74 2 TEMP_CND_ST_A Cond Sat Temp A FLOAT IR
°F 0
°C –17.78
APPENDIX D — MODBUS CONFIGURATION
a
(cont)
ADDRESS
REG. PARAMETER DESCRIPTION
DISPLAY
MODE
(16BITS)
TYPE UNIT
VALUE
COMMENT
HEXADEC. DEC. MIN. MAX. DEFAULT