71
0x004B 75 2 TEMP_DSH_A Discharge Superheat A FLOAT IR
^F 0
^C 0
0x004C 76 2 TEMP_CNDAPP_A Condenser Approach A FLOAT IR
^F 0
^C 0
0x004D 77 2 TEMP_MTRW_A Motor Winding Temp A FLOAT IR
°F 0
°C –17.78
0x004E 78 2 TEMP_ECO_T_A Economizer Gas Temp A FLOAT IR
°F 0
°C –17.78
0x004F 79 2 TEMP_ECOST_A Econ Saturated Temp A FLOAT IR
°F 0
°C –17.78
0x0050 80 2 TEMP_ECO_SH_A Econ Superheat A FLOAT IR
^F 0
^C 0
0x0051 81 2 TEMP_LIQ_T_A Liquid Line Temp A FLOAT IR
°F 0
°C –17.78
0x0052 82 2 TEMP_SLT_A Saturated Liquid Temp A FLOAT IR
°F 0
°C –17.78
0x0053 83 2 TEMP_LLS_A Liquid Line Subcool A FLOAT IR
^F 0
^C 0
0x0054 84 2 TEMP_OILTSMPA Oil Sump Temp A FLOAT IR
°F 0
°C –17.78
0x0055 85 2 TEMP_VAP_TEMP Oil Vaporizer Temp FLOAT IR
°F 0
°C –17.78
0x0056 86 2 TEMP_OIL_A Oil Temp A FLOAT IR
°F 0
°C –17.78
0x0057 87 2 TEMP_EVAP_T_B Evap Rfrg Liq Temp B FLOAT IR
°F 0
°C –17.78
0x0058 88 2 TEMP_EVP_ST_B Evap Saturated Temp B FLOAT IR
°F 0
°C –17.78
0x0059 89 2 TEMP_EVPAPP_B Evaporator Approach B FLOAT IR
^F 0
^C 0
0x005A 90 2 TEMP_SUCT_T_B Suction Temperature B FLOAT IR
°F 0
°C –17.78
0x005B 91 2 TEMP_SST_B Suct Saturated Temp B FLOAT IR
°F 0
°C –17.78
0x005C 92 2 TEMP_SSH_B Suction Superheat B FLOAT IR
^F 0
^C 0
0x005D 93 2 TEMP_DGT_B Discharge Gas Temp B FLOAT IR
°F 0
°C –17.78
0x005E 94 2 TEMP_DIS_ST_B Discharge Sat Temp B FLOAT IR
°F 0
°C –17.78
0x005F 95 2 TEMP_CND_ST_B Cond Sat Temp B FLOAT IR
°F 0
°C –17.78
0x0060 96 2 TEMP_DSH_B Discharge Superheat B FLOAT IR
^F 0
^C 0
0x0061 97 2 TEMP_CNDAPP_B Condenser Approach FLOAT IR
^F 0
^C 0
0x0062 98 2 TEMP_MTRW_B Motor Winding Temp B FLOAT IR
°F 0
°C –17.78
0x0063 99 2 TEMP_ECO_T_B Economizer Gas Temp B FLOAT IR
°F 0
°C –17.78
0x0064 100 2 TEMP_ECOST_B Econ Saturated Temp B FLOAT IR
°F 0
°C –17.78
0x0065 101 2 TEMP_ECO_SH_B Econ Superheat B FLOAT IR
^F 0
^C 0
0x0066 102 2 TEMP_LIQ_T_B Liquid Line Temp B FLOAT IR
°F 0
°C –17.78
0x0067 103 2 TEMP_SLT_B Saturated Liquid Temp B FLOAT IR
°F 0
°C –17.78
0x0068 104 2 TEMP_LLS_B Liquid Line Subcool B FLOAT IR
^F 0
^C 0
0x0069 105 2 TEMP_OILTSMPB Oil Sump Temp B FLOAT IR
°F 0
°C –17.78
0x006A 106 2 TEMP_OIL_B Oil Temp B FLOAT IR
°F 0
°C –17.78
0x006B 107 2 PRESSURE_EVAP_EWP Entering Evap Water Pres FLOAT IR
psig 0
kPa 0
APPENDIX D — MODBUS CONFIGURATION
a
(cont)
ADDRESS
REG. PARAMETER DESCRIPTION
DISPLAY
MODE
(16BITS)
TYPE UNIT
VALUE