0x01DE 478 2 CIRCACTL_ck1avscp cirAActualVarSpdComprCap FLOAT IR ton 0
0x01DF 479 2 CIRCACTL_ck1rfcap cirARunFixSpdComprCap FLOAT IR ton 0
0x01E0 480 2 CIRCACTL_ck1rvcap cirARunVarSpdComprCap FLOAT IR ton 0
0x01E1 481 1 CIRCACTL_cmpn_wrd Compression A Diag Word UINT IR 0
0x01E3 483 1 CIRCACTL_status Circuit A Status UINT IR 0
0x01E4 484 1 CIRCACTL_stdystat Circ A Steady State Flag UINT IR 0 1 0
0x01E5 485 2 OILVCTL_oil_visc Oil Viscosity FLOAT IR 0
0x01E6 486 1 PROTOCOL_MODOCC MODBUS Occupy UINT HR 0 1 0
0x01E7 487 2 PROTOCOL_MODDEML MODBUS Demand Limit FLOAT HR % 40 100 100
0x01E8 488 1 PROTOCOL_MODESTOP MODBUS Estop UINT HR 0 1 0
0x01E9 489 1 PROTOCOL_MODSFTY MODBUS Fire Safety UINT HR 0 1 0
0x01EA 490 1 PROTOCOL_MOD_S_S MODBUS Start/Stop UINT HR 0 1 0
0x01EB 491 1 PROTOCOL_MODLKOUT MODBUS Lockout UINT HR 0 1 0
0x01EE 494 1 EPMPCTL_disc_cmd Evap Pump Cmd UINT IR 0 1 0
0x01EF 495 1 EPMPCTL_dWd Diagnostic Word UINT IR 0
0x01F0 496 1 EPMPCTL_fWd Fault Word UINT IR 0
0x01F1 497 1 EPMPCTL_isEnable Enable UINT IR 0 1 0
0x01F2 498 1 EPMPCTL_isNom Nominal UINT IR 0 1 0
0x01F3 499 1 EPMPCTL_isRd2Go Ready to Start UINT IR 0 1 0
0x01F4 500 1 EPMPCTL_isRd2St Ready to Stop UINT IR 0 1 0
0x01F5 501 1 EPMPCTL_isStart Started UINT IR 0 1 0
0x01F6 502 1 EPMPCTL_isStop Stopped UINT IR 0 1 0
0x01F7 503 1 PLTSPRT_rs485_u1_tres LEN Port J6 Term Res UINT HR 0 1 0
0x01F8 504 1 PLTSPRT_rs485_u3_tres CCN Port J7 Term Res UINT HR 0 1 0
0x01F9 505 1 PLTSPRT_rs485_u4_tres Mod Master J10 Term Res UINT HR 0 1 0
0x01FA 506 1 PLTSPRT_rs485_u5_tres BMS Port J8 Term Res UINT HR 0 1 0
0x01FB 507 1 SERVICE1_flui_typ Evaporator Fluid Type UINT IR 0 2 0
MV: 1=Water, 2=Med
Brine, 3=Low Brine
0x01FC 508 2 SERVICE1_freezesp Brine Freeze Setpoint FLOAT IR
°F –20 34 34
°C –28.89 1.11 1.11
0x01FD 509 2 SERVICE1_min_off Comp Min Off Time FLOAT IR sec 60 1200 120
0x01FE 510 2 SERVICE1_dem_20ma Demand Limit At 20 mA FLOAT IR % 10 100 40
0x01FF 511 2 SERVICE1_min_lwt Minimum Fluid Temp FLOAT IR
°F –20 38 38
°C –28.89 3.33 3.33
0x0200 512 2 SERVICE1_max_lwt Maximum Fluid Temp FLOAT IR
°F 38 153 95
°C 3.33 67.22 35
0x0201 513 1 SERVICE1_emstopen Emergency Stop Enable UINT IR 0 1 1
0x0202 514 2 SERVICE1_rspdmaxA Comp Speed Max A FLOAT IR Hz 132
0x0203 515 2 SERVICE1_rspdmaxB Comp Speed Max B FLOAT IR Hz 132
0x0204 516 1 SERVICE1_ser_pass Service Password UINT IR 0 9999 88
0x0205 517 1 SERVICE1_lockout Service Lockout UINT IR 0 1 0
0x0206 518 1 SERVICE1_rstrtopt Restart Options UINT IR 0 2 0
MV: 0=None, 1=Auto-
Restart, 2=Rapid-
Restart
0x0207 519 1 SERVICE1_stlim_by Starts Limit Bypass UINT IR 0 1
0
0x0208 520 2 SERVICE1_stpperlim_A Starts Per Period Lim FLOAT IR 8
0x0209 521 2 SERVICE1_cmpstper_A Comp Start Period FLOAT IR 3800
0x020A 522 2 SERVICE1_stpperlim_B Starts Per Period Lim FLOAT IR 8
0x020B 523 2 SERVICE1_cmpstper_B Comp Start Period FLOAT IR 3800
0x020C 524 1 SERVICE1_oilsw_by_A Oil Switch Bypass A UINT IR 0 1 0
0x020D 525 1 SERVICE1_oilsw_by_B Oil Switch Bypass B UINT IR 0 1 0
0x020E 526 1 SERVICE1_CirA_En Enable Circuit A UINT IR 0 1 1
0x020F 527 1 SERVICE1_CirB_En Enable Circuit B UINT IR 0 1 1
0x0210 528 1 SERVICE1_rsthrsvc Reset Service Runtime UINT IR 0 1 1
0x0211 529 1 SERVICE1_sftst_en Soft Stop Enable UINT IR 0 1 1
0x0212 530 2 SERVICE1_sftst_th Soft Stop Threshold FLOAT IR % 0 100 50
0x0213 531 1 FACTORY_comp_typ Compressor Type UINT IR 0 4 1
MV: 1=P, 2=Q\R,
3=TC, 4=TD
0x0214 532 1 FACTORY_refrig Refrigerant Type UINT IR 0 15 4
MV: 0=R11, 1=R12,
2=R123, 3=R22,
4=R134A, 5=R404A,
6=R407C, 7=R410A,
8=R454B, 9=R500,
10=R507, 11=R513A,
12=R515A,
13=R515B,
14=R1233ZD,
15=R1234ZE
0x0215 533 1 FACTORY_tons Chiller Tons UINT IR
ton 100 600 100
ton 90.7 544.2 90.7
APPENDIX D — MODBUS CONFIGURATION
a
(cont)
ADDRESS
REG. N° PARAMETER DESCRIPTION
DISPLAY
MODE
(16BITS)
TYPE UNIT
VALUE
COMMENT
HEXADEC. DEC. MIN. MAX. DEFAULT