79
0x0216 534 1 FACTORY_vfd_opt VFD Option UINT IR 0 7 0
MV: 0=None, 1=FS
VFD, 2=Carrier,
3=Rockwell LF2,
4=Eaton, 5=Rockwell
STD, 6=ABB,
7=Danfoss
0x0217 535 1 FACTORY_exv_opt EXV Control Type UINT IR 0 3 0
MV: 0=Disabled,
1=ApprCtrl, 2=EvapLvl,
3=CondLvl
0x0218 536 1 FACTORY_econ_opt Economizer Option UINT IR 0 2 0
MV:0=None, 1=Float,
2=EXV
0x0219 537 1 FACTORY_hgbp_opt HGBP Control Option UINT IR 0 1 0
0x021A 538 1 FACTORY_aux_io Auxilary IO Location UINT IR 0 1 0 0=IOB, 1=Starter
0x021B 539 1 FACTORY_oilassy Oil Assembly Option INT IR 1 2 1
1=one piece vap,
2=two piece vap
0x021C 540 2 ENERGY_din_kw Design Input kW FLOAT IR kW 0
0x021D 541 2 ENERGY_dkw_ton Design Input kW/Ton FLOAT IR kW 0
0x021E 542 2 ENERGY_dewt Design Ent Evap Temp FLOAT IR
°F 0
°C –17.78
0x021F 543 2 ENERGY_dlwt Design Lvg Evap Temp FLOAT IR
°F 0
°C –17.78
0x0220 544 2 ENERGY_degpm Design Evap GPM FLOAT IR
gpm 0
l/min 0
0x0221 545 2 ENERGY_depdft Design Evap Press Drop FLOAT IR
ft 0
m 0
0x0222 546 2 ENERGY_dert Design Evap Refrig Temp FLOAT IR
°F 0
°C –17.78
0x0223 547 2 ENERGY_decwt Design Ent Cond Temp FLOAT IR
°F 0
°C –17.78
0x0224 548 2 ENERGY_dlcwt Design Lvg Cond Temp FLOAT IR
°F 0
°C –17.78
0x0225 549 2 ENERGY_dcgpm Design Cond GPM FLOAT IR
gpm 0
l/min 0
0x0226 550 2 ENERGY_dcpdft Design Cond Press Drop FLOAT IR
ft 0
m 0
0x0227 551 2 ENERGY_dcrt Design Cond Refrig Temp FLOAT IR
°F 0
°C –17.78
0x0228 552 1 HYDRCFG_evapfdtp Evap Flow Detection Type UINT IR 0 2 0
0x0229 553 2 HYDRCFG_evapfldp Evap Min Flow dP FLOAT IR
psig 0 0 0
kPa 0 0 0
0x022A 554 1 HYDRCFG_eflo_vt Evap Flow Verify time UINT IR sec 30 300 30
0x022B 555 1 HYDRCFG_condfdtp Cond Flow Detection Type UINT IR 0 2 0
0x022C 556 2 HYDRCFG_condfldp Cond Min Flow dP FLOAT IR
psig 0 0 0
kPa 0 0 0
0x022D 557 1 HYDRCFG_cflo_vt Cond Flow Verify time UINT IR sec 30 300 30
0x022E 558 1 DRVA1CFG_rlv_i Rated Line Voltage UINT IR V 460
0x022F 559 1 DRVA1CFG_rla_m Motor Rated Load Amps UINT IR amp 10 5000 200
0x0230 560 1 DRVA1CFG_rlv Motor Nameplate Voltage UINT IR V 460
0x0231 561 1 DRVA1CFG_rla Motor Nameplate Current UINT IR amp 200
0x0232 562 1 DRVA1CFG_rlrpm Motor Nameplate RPM UINT IR rpm 3000
0x0233 563 1 DRVA1CFG_rlkw Motor Nameplate KW UINT IR kW 1500
0x0234 564 1 DRVA1CFG_rlhz Compressor 100% Speed UINT IR Hz 0 200 90
0x0235 565 1 DRVA1CFG_min_spd Compressor Unload Spd UINT IR Hz 25
0x0236 566 1 DRVA1CFG_strt_spd Compressor Start Spd UINT IR Hz 25
0x0237 567 2 DRVA1CFG_torq_lim Torque Limit Percent FLOAT IR % 115
0x0238 568 2 DRVA1CFG_curr_lim Current Limit Percent FLOAT IR % 110
0x0239 569 2 DRVA1CFG_pwm_freq PWM Switch Frequency FLOAT IR 0 0 2
0x023A 570 2 DRVA1CFG_skipfrq1 Skip Frequency 1 FLOAT IR Hz 102
0x023B 571 2 DRVA1CFG_skipfrq2 Skip Frequency 2 FLOAT IR Hz 102
0x023C 572 2 DRVA1CFG_skipfrq3 Skip Frequency 3 FLOAT IR Hz 102
0x023D 573 2 DRVA1CFG_skipband Skip Frequency Band FLOAT IR Hz 0
0x023E 574 1 DRVA1CFG_ramp_inc Increase Ramp Time UINT IR sec 30
0x023F 575 1 DRVA1CFG_ramp_dec Decrease Ramp Time UINT IR sec 30
0x0240 576 2 SETPOINT_lcw_sp Cooling LCW Setpoint FLOAT HR
°F 10 120 45
°C –12.22 48.89 7.22
0x0241 577 2 SETPOINT_ice_sp Ice Build Setpoint FLOAT HR
°F 15 60 40
°C –9.44 15.56 4.44
0x0242 578 1 SETPOINT_EWT_OPT EWT Control Option UINT HR 0 1 0
APPENDIX D — MODBUS CONFIGURATION
a
(cont)
ADDRESS
REG. N° PARAMETER DESCRIPTION
DISPLAY
MODE
(16BITS)
TYPE UNIT
VALUE
COMMENT
HEXADEC. DEC. MIN. MAX. DEFAULT