0x0243 579 2 SETPOINT_ecw_sp Cooling ECW Setpoint FLOAT HR
°F 15 120 60
°C –9.44 48.89 15.56
0x0244 580 2 SETPOINT_dem_base Base Demand Limit FLOAT HR % 25 100 100
0x0245 581 2 SETPOINT_rcyc_lo Recycle Shutdown Offset FLOAT HR
°F 0 10 5
°C –17.78 –12.22 –15
0x0246 582 2 SETPOINT_rcyc_hi Recycle Startup Offset FLOAT HR
°F 0 10 5
°C –17.78 –12.22 –15
0x0247 583 1 ALARMRST_RST_ALM Alarm Reset UINT IR 0 1 0
0x0249 585 1 ALARMRST_alarm_1 Jbus Current Alarm 1 UINT IR 0
0x024A 586 1 ALARMRST_alarm_2 Jbus Current Alarm 2 UINT IR 0
0x024B 587 1 ALARMRST_alarm_3 Jbus Current Alarm 3 UINT IR 0
0x024C 588 1 ALARMRST_alarm_4 Jbus Current Alarm 4 UINT IR 0
0x024D 589 1 ALARMRST_alarm_5 Jbus Current Alarm 5 UINT IR 0
NOTE(S):
a. Not all points are applicable to 23XRV; this list is common between products sharing the same software platform.
APPENDIX D — MODBUS CONFIGURATION
a
(cont)
ADDRESS
REG. N° PARAMETER DESCRIPTION
DISPLAY
MODE
(16BITS)
TYPE UNIT
VALUE
COMMENT
HEXADEC. DEC. MIN. MAX. DEFAULT
LEGEND
CO — COILS_MEDIA
DEC — Decimal
DI — DISCR_INPUT_MEDIA
HEXIDEC — Hexadecimal
HR — HOLDING_REG_MEDIA
IR — INPUT_REG_MEDIA
MV — Multi-State Value