148
Table 6 — 30XA080-500 Electrical Data, Dual Point (Standard Condenser Fan Motors) (cont)
LEGEND NOTES:
1. Units are suitable for use on electrical systems where voltage supplied to the unit terminals
is not below or above the listed minimum and maximum limits. Maximum allowable phase
imbalance is: voltage, 2%; amps 10%.
2. Cooler heater is wired into the control circuit so it is always operable as long as the control
power supply disconnect is on, even if any safety device is open.
3. For MCA
that is less than or equal to 380 amps, 3 conductors are required.
For MCA between 381 and 760 amps, 6 conductors are required.
For MCA between 761 and 1140 amps, 9 conductors are required.
For MCA between 1141 and 1520 amps, 12 conductors are required.
Calculation of conductors required is based on 75 C copper wire.
4. Wiring for main field supply must be rated 75 C minimum. Use copper for all units.
a
. Incoming wire size range for the terminal block is no. 4 AWG (American Wire Gage) to
500 kcmil.
b. Incoming wire size range of non-fused disconnect with MCA up to 599.9 amps is 3/0 to
500 kcmil.
c. Incoming wire size range of non-fused disconnect with MCA from 600 to 799.9 amps is 1/
0 to 500 kcmil.
d. Incoming wire size range of non-fused disconnect with MCA from 800 to 1199.9 amps is
250 kcmil to 500 kcm
il.
5. Data provided circuit 1/circuit 2 where there are two circuits.
6. Standard condenser fan motors are not used with sizes 30XA-401, 451, 476, and 501.
These sizes use high ambient temperature condenser fans.
UNIT
30XA
UNIT VOLTAGE
NUMBER
OF
COND
FANS
15 HP PUMP, 3450 RPM CONTROL CIRCUIT
V-Hz
(3 Ph)
Supplied
MCA MOCP
ICF Rec
Fuse
Size
Voltage
1 PH,
60 Hz
MCA
and
MOCP
Min Max WD XL
080,
082
230-60 207 253 3/3 — — — — — 115 40
200-60 1
87 220 3/3 — — — — — 115 40
460-60 414 506 3/3 — — — — — 115 40
575-60 518 633 3/3 — — — — — 115 40
380-60 342 418 3/3 — — — — — 115 40
090,
092
230-60 207 253 4/4 182.9/227.9 300/350 348.0/393.0 1034.0/1079.0 225/300 115 40
200-60 187 220 4/4 201.5/251.2 300/350 399.5/449.3 1188.5/1238.3 250/300 115 40
460-60 414 506 4/4 91.4/113.9 150/175 174.0/196.5 517.0/ 539.5 110/150 115 40
575-60 518 633 4/4 70.3/ 88.3 110/125 139.6/157.6 413.6/ 431.6 90/110 115 40
380-60 342 418 4/4 106.5/133.7 175/20
0 210.5/237.8 625.5/ 652.8 125/175 115 40
100,
102
230-60 207 253 4/4 199.9/244.9 300/350 372.0/417.0 1114.0/1159.0 250/300 115 40
200-60 187 220 4/4 220.0/269.8 350/400 426.5/476.3 1280.5/1330.3 300/350 115 40
460-60 414 506 4/4 99.9/122.4 150/175 186.0/208.5 557.0/ 579.5 125/150 115 40
575-60 518 633 4/4 76.4/ 94.4 125/125 148.6/166.6 445.6/ 463.6 90/110 115 40
380-60 342 418 4/4 116.5/143.8 175/225 225.5/252.8 674.5/ 701.8 150/175 115 40
110,
112
230-60 207 253 4/4 2
41.0/244.9 400/350 372.0/417.0 — 300/300 115 40
200-60 187 220 4/4 264.9/269.8 450/400 426.5/476.3 — 350/350 115 40
460-60 414 506 4/4 120.0/122.4 200/175 186.0/208.5 557.0/ 579.5 150/150 115 40
575-60 518 633 4/4 92.5/ 94.4 150/125 148.6/166.6 445.6/ 463.6 110/110 115 40
380-60 342 418 4/4 140.2/143.8 225/225 225.5/252.8 674.5/ 701.8 175/175 115 40
120,
122
230-60 207 253 4/4 241.0/286.0 400/450 372.0/417.0 — 300/350 115 40
200-60 187 220 4/4 264.9/314.7 450/500 426.5/
476.3 — 350/400 115 40
460-60 414 506 4/4 120.0/142.5 200/225 186.0/208.5 557.0/ 579.5 150/175 115 40
575-60 518 633 4/4 92.5/110.5 150/175 148.6/166.6 445.6/ 463.6 110/150 115 40
380-60 342 418 4/4 140.2/167.5 225/250 225.5/252.8 674.5/ 701.8 175/200 115 40
140,
142
230-60 207 253 6/4 370.0/244.9 600/350 632.0/417.0 — 450/300 115 40
200-60 187 220 6/4 407.2/269.8 700/400 724.8/476.3 — 500/350 115 40
460-60 414 506 6/4 185.0/122.4 300/175 316.0/208.5 948.0/ 579.5 225/15
0 115 40
575-60 518 633 6/4 141.9/ 94.4 225/125 252.4/166.6 758.4/ 463.6 175/110 115 40
380-60 342 418 6/4 215.1/143.8 350/225 382.8/252.8 1147.8/ 701.8 300/175 115 40
160,
162
230-60 207 253 6/4 423.5/286.0 700/450 800.0/417.0 — 600/350 115 40
200-60 187 220 6/4 465.6/314.7 800/500 918.8/476.3 — 600/400 115 40
460-60 414 506 6/4 211.3/142.5 350/225 400.0/208.5 1208.0/ 579.5 250/175 115 40
575-60 518 633 6/4 162.2/110.5 250/175 320.4/166.6 966.4/ 463.6 200/150 115 40
380-
60 342 418 6/4 246.0/167.5 400/250 483.8/252.8 1462.8/ 701.8 300/200 115 40
180,
182
230-60 207 253 6/6 — — — — — 115 60
200-60 187 220 6/6 — — — — — 115 60
460-60 414 506 6/6 — — — — — 115 60
575-60 518 633 6/6 — — — — — 115 60
380-60 342 418 6/6 — — — — — 115 60
200,
202
230-60 207 253 6/6 — — — — — 115 60
200-60 187 220 6/6 — — — — — 115 60
460-60 414 506 6/6 — — — — — 115 60
575-60 518 633 6/6 — — — — — 115 60
380-60 342 418 6/6 — — — — — 115 60
220,
222
230-60 207 253 7/6 — — — — — 115 60
200-60 187 220 7/6 — — — — — 115 60
460-60 414 506 7/6
— — — — — 115 60
575-60 518 633 7/6 — — — — — 115 60
380-60 342 418 7/6 — — — — — 115 60
240,
242
230-60 207 253 7/6 — — — — — 115 60
200-60 187 220 7/6 — — — — — 115 60
460-60 414 506 7/6 — — — — — 115 60
575-60 518 633 7/6 — — — — — 115 60
380-60 342 418 7/6 — — — — — 115 60
260,
262
460-60 414 506 9/6 — — — — — 115 60
575-60 518 633 9/6 — — — — — 115 60
380-60 342 418 9/6 — — — — — 115 60
280,
282
460-60 414 506 9/7 — — — — — 115 60
575-60 518 633 9/7 — — — — — 115 60
380-60 342 418 9/7 — — — — — 115 60
300,
302
460-60 414 506 10/6 — — — — — 115 60
575-60 518 63
3 10/6 — — — — — 115 60
380-60 342 418 10/6 — — — — — 115 60
325,
327
460-60 414 506 9/9 — — — — — 115 60
575-60 518 633 9/9 — — — — — 115 60
380-60 342 418 9/9 — — — — — 115 60
350,
352
460-60 414 506 9/9 — — — — — 115 60
575-60 518 633 9/9 — — — — — 115 60
380-60 342 418 9/9 — — — — — 115 60
400
460-60 414 506 8/12 — — — — — 115 60
575-60 518 633 8/12 — — — — — 115 60
380-60 342 418 8/12 — — — — — 115 60
ICF — Instantaneous Current Flow
MCA — Minimum Circuit Amps
MOCP — Maximum Overcurrent Protection
WD — Wye-Delta
XL — Across-the-Line