150
Table 7 — 30XA140-501 Electrical Data, Single Point (High Ambient Option)
LEGEND
NOTES:
1. Units are suitable for use on electrical systems where voltage supplied to the unit termi-
nals is not below or above the listed minimum and maximum limits. Maximum allowable
phase imbalance is: voltage, 2%; amps 10%.
2. Cooler heater is wired into the control circuit so it is always operable as long as the con-
trol power supply disconnect is on, even if any safety device is open.
3. For
MCA that is less than or equal to 380 amps, 3 conductors are required.
For MCA between 381 and 760 amps, 6 conductors are required.
For MCA between 761 and 1140 amps, 9 conductors are required.
For MCA between 1141 and 1520 amps, 12 conductors are required.
Calculation of conductors required is based on 75 C copper wire.
4. Wiring for main field supply must be rated 75 C minimum. Use copper for all uni
ts.
a. Incoming wire size range for the terminal block is no. 4 AWG (American Wire Gage)
to 500 kcmil.
b. Incoming wire size range of non-fused disconnect with MCA up to 599.9 amps is 3/0
to 500 kcmil.
c. Incoming wire size range of non-fused disconnect with MCA from 600 to 799.9 amps
is 1/0 to 500 kcmil.
d. Incoming wire size range of non-fused disconnect with MCA from 800 to 1199.9 amps
is 250 kcmil to 500
kcmil.
5. Data provided circuit 1/circuit 2 where there are two circuits.
UNIT
30XA
UNIT VOLTAGE
NUMBER
OF
COND
FANS
NO HYDRONIC PACKAGE 5 HP PUMP, 3450 RPM 7.5 HP PUMP, 3450 RPM CONTROL CIRCUIT
V-Hz
(3 Ph)
Supplied
MCA MOCP
ICF Rec
Fuse
Size
MCA MOCP
ICF Rec
Fuse
Size
MCA MOCP
ICF Rec
Fuse
Size
Voltage
1 PH,
60 Hz
MCA
and
MOCP
Min Max WD XL WD XL WD XL
140,
142
230-60 207 253 10 562.0 800 838.9 — 700 578.0 800 854.9 — 700 585.2 800 862.1 — 700 115 40
200-60 187
220 10 618.8 800 952.8 — 700 636.5 800 970.5 — 800 644.4 800 978.5 — 800 115 40
460-60 414 506 10 281.0 400 419.5 1051.5 350 289.0 400 427.5 1059.5 350 292.6 400 431.1 1063.1 350 115 40
575-60 518 633 10 216.3 300 332.5 838.5 250 222.7 300 338.9 844.9 250 225.6 300 341.8 847.8 250 115 40
380-60 342 418 10 328.3 450 504.6 1269.6 400 338.0 450 514.3 1279.3 400 342.3 450 518.7 1283.7 400 115 40
160,
162
230-60 207 253 10 642.7 800 1036.7 — 800 658.7 800 1052.7 — 800 665.9 800 1059.9 — 800 115 40
200-60 1
87 220 10 706.9 1000 1179.4 — 800 724.5 1000 1197.1 — 1000 732.5 1000 1205.0 — 1000 115 40
460-60 414 506 10 320.5 450 518.0 1326.0 400 328.5 450 526.0 1334.0 400 332.1 450 529.6 1337.6 400 115 40
575-60 518 633 10 247.2 350 412.1 1058.1 300 253.6 350 418.5 1064.5 300 256.5 350 421.4 1067.4 300 115 40
380-60 342 418 10 374.9 500 622.8 1601.8 450 384.6 500 632.5 1611.5 450 388.9 500 636.8 1615.8 450 115 40
180,
182
230-60 207 253 12 703.9 800 980.8 — 800 — — — — — — — — — — 115 60
200-60 187 220 12 775.0 10
00 1109.1 — 1000 — — — — — — — — — — 115 60
460-60 414 506 12 351.9 450 490.4 1122.4 400 — — — — — — — — — — 115 60
575-60 518 633 12 271.1 350 387.3 893.3 300 — — — — — — — — — — 115 60
380-60 342 418 12 410.8 500 587.2 1352.2 450 — — — — — — — — — — 115 60
200,
202
230-60 207 253 12 795.6 1000 1189.6 — 1000 — — — — — — — — — — 115 60
200-60 187 220 12 875.0 1200 1347.5 — 1000 — — — — — — — — — — 115 60
460-60 414 506 12 396.9 500 594.4 1402.4 450 — — — — — — — — — — 115 60
575-60 518 633 12 305.8 400 470.7 1116.7 350 — — — — — — — — — — 115 60
380-60 342 418 1
2 463.8 600 711.7 1690.7 600 — — — — — — — — — — 115 60
220,
222
230-60 207 253 13 876.7 1200 1200.4 — 1000 — — — — — — — — — — 115 60
200-60 187 220 13 964.6 1200 1359.4 — 1200 — — — — — — — — — — 115 60
460-60 414 506 13 438.0 600 599.8 1407.8 500 — — — — — — — — — — 115 60
575-60 518 633 13 337.6 450 475.0 1121.0 400 — — — — — — — — — — 115 60
380-60 342 418 13 511.5 700 718.3 1697.3 600 — — — — — — — — — — 115 60
240,
242
230-60 207 253 13 933.0 1200 1256.7 — 1200 — — — — — — — — — — 115 60
200-60 187 220 13 1026.7 1200 1421.6 — 1200 — — — — — — — — — — 115
60
460-60 414 506 13 466.5 600 628.3 1436.3 600 — — — — — — — — — — 115 60
575-60 518 633 13 359.5 450 497.0 1143.0 400 — — — — — — — — — — 115 60
380-60 342 418 13 544.4 700 751.2 1730.2 600 — — — — — — — — — — 115 60
260,
262
460-60 414 506 15 529.1 700 806.6 2028.6 600 — — — — — — — — — — 115 60
575-60 518 633 15 407.4 500 639.7 1617.7 500 — — — — — — — — — — 115 60
380-60 342 418 15 616.7 800 969.3 2448.3 700 — — — — — — — — — — 115 60
280,
282
460-60 414 506 16 563.0 800 840.5 2062.5 700 — — — — — — — — — — 115 60
575-60 518 633 16 433.6 600 665.9
1643.9 500 — — — — — — — — — — 115 60
380-60 342 418 16 656.2 800 1008.8 2487.8 800 — — — — — — — — — — 115 60
300,
302
460-60 414 506 16 619.6 800 840.5 2062.5 700 — — — — — — — — — — 115 60
575-60 518 633 16 476.7 600 665.9 1643.9 600 — — — — — — — — — — 115 60
380-60 342 418 16 722.3 1000 1008.8 2487.8 1000 — — — — — — — — — — 115 60
325,
327
460-60 414 506 18 638.1 800 915.6 2137.6 700 — — — — — — — — — — 115 60
575-60 518 633 18 491.2 600 723.5 1701.5 600 — — — — — — — — — — 115 60
380-60 342 418 18 743.0 1000 1095.6 2574.6 1000 — — — — — — — — — — 115
60
350,
352
460-60 414 506 18 694.6 800 915.6 2137.6 800 — — — — — — — — — — 115 60
575-60 518 633 18 534.2 700 723.5 1701.5 600 — — — — — — — — — — 115 60
380-60 342 418 18 809.1 1000 1095.6 2574.6 1000 — — — — — — — — — — 115 60
400
460-60 414 506 20 760.8 1000 1038.3 2260.3 1000 — — — — — — — — — — 115 60
575-60 518 633 20 585.7 700 818.1 1796.1 700 — — — — — — — — — — 115 60
380-60 342 418 20 886.5 1000 1239.1 2718.1 1000 — — — — — — — — — — 115 60
401
460-60 414 506 20 853.6 1200 1018.6 2299.6 1000 — — — — — — — — — — 115 60
575-60 518 633 20
671.6 800 802.6 1825.6 800 — — — — — — — — — — 115 60
380-60 342 418 20 1017.7 1200 1219.6 2773.6 1200 — — — — — — — — — — 115 60
450
460-60 414 506 22 889.1 1000 1110.0 2332.0 1000 — — — — — — — — — — 115 60
575-60 518 633 22 683.4 800 872.7 1850.7 800 — — — — — — — — — — 115 60
380-60 342 418 22 1035.9 1200 1322.4 2801.4 1200 — — — — — — — — — — 115 60
451
460-60 414 506 22 864.4 1200 1029.4 2310.4 1000 — — — — — — — — — — 115 60
575-60 518 633 22 680.2 800 811.2 1834.2 800 — — — — — — — — — — 115 60
380-60 342 418 22 1
030.8 1200 1232.7 2786.7 1200 — — — — — — — — — — 115 60
476
460-60 414 506 22 861.5 1200 1055.4 2336.4 1000 — — — — — — — — — — 115 60
575-60 518 633 22 687.2 800 840.5 1863.5 800 — — — — — — — — — — 115 60
380-60 342 418 22 1046.2 1200 1280.1 2834.1 1200 — — — — — — — — — — 115 60
500
460-60 414 506 22 937.6 1200 1158.5 2380.5 1200 — — — — — — — — — — 115 60
575-60 518 633 22 720.8 800 910.0 1888.0 800 — — — — — — — — — — 115 60
380-60 342 418 22 1092.4 1200 1378.8 2857.8 1200 — — — — — — — — — — 115 60
501
460-60 414 506 26 912.9 12
00 1077.9 2358.9 1200 — — — — — — — — — — 115 60
575-60 518 633 26 729.1 1000 860.1 1883.1 1000 — — — — — — — — — — 115 60
380-60 342 418 26 — — — — — — — — — — — — — — — 115 60
ICF — Instantaneous Current Flow
MCA — Minimum Circuit Amps
MOCP — Maximum Overcurrent Protection
WD — Wye-Delta
XL — Across-the-Line