EasyManua.ls Logo

Carrier Aquaforce 30XA Series - Page 156

Carrier Aquaforce 30XA Series
162 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
156
Table 9 — Compressor and Fan Electrical Data (cont)
LEGEND
*Quantity of fan motors for incoming power supply Circuit 1/Circuit 2.
NOTES:
1. For 30XA080-352, 401, 451, and 476 units with dual power supply, main power supply 1
uses refrigerant circuit A components to calculate MCA and MOCP. Main power supply 2
uses refrigerant circuit B components to calculate MCA and MOCP.
2. 30XA400, 450, and 500 units have dual power supply. Main power supply 1 u
ses refriger-
ant circuit C components to calculate MCA and MOCP. Main power supply 2 uses refriger-
ant circuit A and B components to calculate MCA and MOCP.
Table 10 — Pump Electrical Data
FLA — Full Load Amps
30XA
UNIT
SIZE
UNIT
VOLTAGE
V-Hz
(3 Ph,
60 Hz)
NUMBER
OF COND
FANS*
CONDENSER
FANS
COMPRESSOR
A B C
LRA (All Units) RLA LRA (All Units) RLA LRA (All Units) RLA
FLA
XL WD
High
Ambient
Temp
Cond. Fans
(1140 rpm)
Standard
Cond. Fans
(850 rpm)
XL WD
H
igh
Ambient
Temp
Cond. Fans
(1140 rpm)
Standard
Cond. Fans
(850 rpm)
XL WD
High
Ambient
Temp
Cond. Fans
(1140 rpm)
Standard
Cond. Fans
(850 rpm)
High
Ambient
Temp
Cond. Fans
(1140 rpm)
Standard
Cond. Fans
(850 rpm)
401
380 11/9 6.5 2312 758 449.8 2179 700 418.9
460 11/9 5.4 1906 625 371.0 1800 578 346.3
575 11/9 4.3 1521 498 294.8 1440 462 275.0
450
380 8/14 6.5 3.6 2179 700 330.8 350.3 1126 361 147.7 154.6 2179 700 3
30.8 350.3
460 8/14 5.4 3.0 1800 578 285.6 302.4 930 298 127.6 133.6 1800 578 285.6 302.4
575 8/14 4.3 2.4 1440 462 218.2 231.0 744 238 97.5 102.0 1440 462 218.2 231.0
451
380 13/9 6.5 2312 758 529.4 2179 700 403.9
460 13/9 5.4 1906 625 438.2 1800 578 346.3
575 13/9 4.3 1521 498 349.5 1440 462 266.4
476
380 11/11 6.5 2312 756 490.8 2312 758 449.8
460 11/11 5.4 1906 625 404.3 1906 625 371.0
575 11/11 4.3 1521 498 323.0 1521 498 294.8
500
380 8/14 6.5 3.6 2179 700 330.8 350.3 1441 462 204.2 214.3 2179 700 330.8 350.3
460 8/14 5.4 3.0 1800 578 285.6 302.4 1190 382 176.1 184.9 1800 578 285.6 302.4
575 8/14 4.3 2.4 1440 462 218.2 231.0 952 306 134.8 141.5 1440 462 218.2 231.0
501
380 14/12 6.5 2312 758 535.9 2312 758 497.3
460 14/12 5.4 1906 625 443.6 1906 625 409.7
575 14/12 4.3 1521 498 353.8 1521 498 327.3
LRA Locked Rotor Amps WD Wye Delta
RLA Rated Load Amps XL Across-the-Line
PUMP
HP
UNIT VOLTAGE
V-Hz (3 Ph)
HYDRONIC SYSTEM (SINGLE OR DUAL)
FLA (Each)
30XA
UNIT SIZE
5
230-60 11.6
090-162
200-60 12.6
460-60 5.8
575-60 4.6
380-60 7.0
7.5
230-60 17.4
090-162
200-60 18.5
460-60 8.7
575-60 7.0
380-60 10.4
10
230-60 23.0
090-162
200-60 25.0
460-60 11.5
575-60 9.2
380-60 14.0
15
230-60 34.0
090-162
200-60 36.7
460-60 17.0
575-60 14.0
380-60 21.0

Related product manuals