1.125" KNOCKOUT
MAIN POWER ENTRY
HIGH SHORT CIRCUIT
CURRENT RATING OPTION
460 AND 575 VOLT
NEXT PAGE
Fig. 12 30XA182,202 Air-Cooled Liquid Chiller Dimensions
30XA UNIT
CENTER OF GRAVITY
CGx CGy
182 138.0 [3505.2] 38.0 [965.2]
202 138.0 [3505.2] 38.0 [965.2]
a30-5482
CONTROL BOX A B
STD BOX
22.04
[568.96]
7.87
[199.89]
HSCCR BOX
14.04
[356.61]
6.74
[171.19]
NOTES:
1. Unit must have clearances as follows:
Top Do not restrict
Sides and End 6 ft (1.8 m) from solid surface.
For airflow side 8 ft (2.4 m) required for surface area.
2. Temperature relief devices are located on liquid line and
economizer assemblies and have
1
/
4
-in. flare connection.
3. Pressure relief devices are located on the cooler (
5
/
8
-in. NPT
male connector) and on each oil separator (
3
/
8
-in. flare
connection).
4. Dimensions are shown in inches. Dimensions in [ ] are in
millimeters.