94
DUAL PUMP UNITS — ENGLISH
DUAL PUMP UNITS — SI
30XA
UNIT SIZE
MOUNTING WEIGHT (lb) — Al/Cu*
A B C D E F Total
090 1273 3106 1248 972 2089 1271 9,959
092 1289 3145 1264 984 2115 1287 10,083
100 1299 3168 1285 997 2140 1297 10,186
102 1315 3206 1301 1009 2166 1313 10,310
110 1312 3211 1307 1019 2175 1303 10,326
112 1342 3285 1337 1042 2225 1333 10,563
120 1346 3249 1310 1021 2208 1337 10,471
122 1373 3314 1336 1041 2252 1364 10,681
30XA
UNIT SIZE
MOUNTING WEIGHT (lb) — Al/Cu*
A B C D E F G H Total
140 2007 1554 1891 1768 1152 883 1695 1809 12,760
142 2079 1610 1959 1831 1193 915 1756 1874 13,217
160 20
61 1581 1909 1799 1178 898 1715 1862 13,003
162 2129 1633 1972 1858 1217 927 1771 1923 13,429
30XA
UNIT SIZE
MOUNTING WEIGHT (kg) — Al/Cu*
A B C D E F Total
090 578 1409 566 441 947 576 4517
092 585 1426 573 446 959 584 4573
100 589 1437 583 452 971 588 4620
102 596 1454 590 458 982 595 4676
110 595 1456 593 462 986 591 4684
112 609 1490 606 473 1009 605 4791
120 611 1474 594 463 1001 607 4750
122 623 1503 606 472 1022 619 4845
30XA
UNIT SIZE
MOUNTING WEIGHT (kg) — Al/Cu*
A B C D E F G H Total
140 910 705 858 802 523 401 769 821 5788
142 943 730 888 831 541 415 796 850 599
5
160 935 717 866 816 534 408 778 845 5898
162 965 741 894 843 552 421 803 872 6091
30XA090-122
30XA140-162
Fig. 28B — Unit Mounting Weights (Units with Al/Cu Condensers) (cont)
a30-4420 a30-4421
ABC
FED
COOLER SIDE
COMPRESSOR SIDE
ABCD
HGFE
COOLER SIDE
COMPRESSOR SIDE
LEGEND
*Condenser : Aluminum Fins/Copper Tubing.
Al Aluminum
Cu Copper