Catalog No. 04-53300247-01 Printed in U.S.A. Form No. 30RC-100SI Pg 1 2-24 Replaces: NEW
Installation Instructions
CONTENTS
Page
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . 1
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Storage Recommendations . . . . . . . . . . . . . . . . . . . . 2
PROVIDE MACHINE PROTECTION
EVAPORATOR PROTECTION
INSPECTION DURING STORAGE
Step 1 — Place and Rig the Unit . . . . . . . . . . . . . . . . 3
•PLACING UNIT
•RIGGING
MOUNTING UNIT
Step 2 — Check Compressor Mounting . . . . . . . . . 16
Step 3 — Connect Evaporator Fluid and
Drain Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
ALL UNITS
VICTAULIC COUPLING INSTALLATION
UNITS WITH FACTORY-INSTALLED HYDRONIC
PACKAGES
•AIR SEPARATION
Step 4 — Fill the Chilled Water Loop . . . . . . . . . . . 29
WATER SYSTEM CLEANING
FILLING THE SYSTEM
PREPARATION FOR YEAR-ROUND OPERATION
FREEZE PROTECTION
PREPARATION FOR WINTER SHUTDOWN
Step 5 — Make Electrical Connections . . . . . . . . . . 36
POWER SUPPLY
•POWER WIRING
CONTROL POWER
Step 6 — Install Accessories . . . . . . . . . . . . . . . . . . 48
ELECTRICAL
Step 7 — Check Refrigerant Circuit . . . . . . . . . . . . 48
DETECTION OF FLAMMABLE REFRIGERANTS
REMOVAL AND EVACUATION
CHARGING PROCEDURES
RECOVERY
CARRIER COMFORT NETWORK
®
(CCN)
COMMUNICATION BUS WIRING
BACNET IP, MSTP OR ETHERNET COMMUNICATION
NON-CCN COMMUNICATION WIRING
MS/TP WIRING RECOMMENDATIONS
APPENDIX A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
SAFETY CONSIDERATIONS
Installing, starting up, and servicing air-conditioning equipment
can be hazardous due to system pressures, electrical components,
and equipment location.
Only trained, qualified installers and service mechanics should
install, start up, and service this equipment.
Untrained personnel can perform basic maintenance functions,
such as cleaning coils. All other operations should be performed
by trained service personnel. Qualified installers and service tech-
nicians are required to have been trained on the following topics
when installing and servicing air-conditioning equipment with
A2L refrigerant such as R-32:
1. Explosive potential of A2L refrigerants
2. Potential ignition sources
3. Safety measures for unventilated and ventilated rooms or
enclosures
4. Refrigerant detectors
5. Concept of sealed components and sealed enclosures
according to IEC 60079-15:2010
6. Correct work procedures for the following:
a. Commissioning
b. Maintenance
c. Repair
d. Decommissioning
e. Disposal
Refer to Controls and Troubleshooting Guide for complete guide-
lines. When working on the equipment, observe precautions in the
literature and on tags, stickers, and labels attached to the
equipment.
1. Follow all safety codes.
2. Keep quenching cloth and fire extinguisher nearby when
brazing.
3. Wear safety glasses and work gloves.
4. Use care in handling, rigging, and setting bulky equipment.
It is important to recognize safety information. This is the safety-
alert symbol . When you see this symbol on the unit and in in-
structions or manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, CAUTION,
and NOTE. These words are used with the safety-alert symbol.
DANGER identifies the most serious hazards which will result in
severe personal injury or death. WARNING signifies hazards
which could result in personal injury or death. CAUTION is used
to identify unsafe practices, which may result in minor personal
injury or product and property damage. NOTE is used to highlight
suggestions which will result in enhanced installation, reliability,
or operation.
AquaSnap
®
30RC010-060 Air-Cooled Chillers
with Greenspeed Technology
Question and Answer IconNeed help?

Do you have a question about the Carrier AquaSnap 30RC010 and is the answer not in the manual?

Overview

The Carrier AquaSnap® 30RC010-060 Air-Cooled Chillers with Greenspeed Technology are designed for outdoor installations and provide chilled liquid for various applications. These units are suitable for use with A2L refrigerants, specifically R-32, which requires adherence to specific safety guidelines due to its explosive potential and flammability.

Function Description:

These chillers are air-cooled liquid chillers that utilize Greenspeed Technology for enhanced efficiency. They are equipped with factory-installed strainers (including a blow-down valve) in the entering fluid piping and a flow switch in the leaving fluid piping. The flow switch wiring is factory installed. The units can be configured with various options, including different condenser coil types (MCHX or Al-Cu), single or dual hydronic pump packages, and digital compressors. They also offer sound options for low noise operation and compressor blankets. The control system, PIC6, can be integrated with Energy Management Modules (EMM), BACnet IP/MSTP, Ethernet, and remote connectivity for comprehensive control and monitoring.

Important Technical Specifications:

  • Unit Sizes: 010-060, with varying capacities (e.g., 10 tons for 010, 30 tons for 060).
  • Voltage Options: 575-3-60, 380-3-60, 208/230-3-60, 460-3-60.
  • Refrigerant Type: R-32, EXV Controlled System.
  • Refrigerant Charge (MCHX Coil): Ranges from 7.50 lb (3.4 kg) for 010 to 28.00 lb (12.25 kg) for 060.
  • Refrigerant Charge (RTPF Coil): Ranges from 15.50 lb (8 kg) for 010 to 58.00 lb (24 kg) for 060.
  • Compressors: Scroll, Hermetic type, with 2 or 4 compressors depending on unit size. Speed is 3500 rpm (58.3 R/s).
  • Evaporator: Brazed, Direct-Expansion Plate Heat Exchanger.
  • Maximum Refrigerant Pressure: 710 psig (4481 kPa).
  • Maximum Water-Side Pressure: 300 psig (2068 kPa) without pump, 150 psig (1034 kPa) with pump.
  • Chilled Water Connections: 2-inch or 2.5-inch Victaulic (IPS Carbon Steel) for inlet and outlet.
  • Drain: 0.25-inch NPT.
  • Condenser Fans: Axial Vertical Discharge, Composite type. Fan speed is 850 rpm. Total airflow ranges from 9,400 cfm for 010 to 38,500 cfm for 060.
  • Hydronic Pump Package (Optional): Single or Dual, Centrifugal Monocell Pump(s), 3500 RPM. Expansion tank volume ranges from 4.4/3.2 gal (16.7/12.11 L) for 010-025 to 10.3/10.3 gal (38.9/38.9 L) for 030-060.
  • Minimum Circuit Amps (MCA) and Maximum Overcurrent Protection (MOCP): Vary significantly based on unit size, voltage, compressor type (standard or digital), and pump options. For example, a 30RC010 standard compressor unit at 208/230V with no pump has an MCA of 51.7A and MOCP of 70A.
  • Recommended Separation: Minimum 6 ft (1829 mm) when coils face each other; 3.5 ft (1067 mm) when one coil faces a wall. Minimum 4 ft (1219 mm) clearance on the side with the electrical box.

Usage Features:

  • Outdoor Installation: Designed for robust outdoor operation.
  • Parallel Chiller Control: Supports dual chiller algorithms for parallel operation, requiring an additional chilled water sensor in the common leaving water header.
  • Hydronic Package Options: Available with factory-installed hydronic packages, including pumps, strainers, expansion tanks, and flow switches, simplifying installation for closed systems.
  • Communication Options: Integrates with Carrier Comfort Network® (CCN), BACnet IP, MSTP, and Ethernet for flexible building management system integration.
  • Energy Management Module (EMM): Provides advanced features like temperature reset, demand limit, and ice features.
  • Digital Compressor Option: Offers enhanced capacity control and efficiency.
  • Low Sound Option: Available for noise-sensitive environments.
  • Greenspeed Technology: Optimizes performance and energy efficiency.

Maintenance Features:

  • Storage Recommendations: Guidelines for protecting the unit from vandalism, accidental contact, falling debris, and construction waste during storage.
  • Evaporator Protection: Recommendations for treating the evaporator and associated piping to prevent corrosion and freezing, including the use of inhibited glycol solutions or complete water removal and nitrogen pressurization.
  • Inspection During Storage: Regular checks (every 3 or 6 months) for refrigerant pressure, physical damage, and moisture in the control box.
  • Water System Cleaning: Detailed procedures for cleaning the chilled water loop, including temporary bypass installation, use of cleaning agents, and side stream filtration. Water quality characteristics and limitations are provided to prevent heat exchanger failure.
  • Air Separation: Instructions for managing air in the system, including installing automatic air vents at high points and air separators in the return piping.
  • Freeze Protection: Recommendations for using inhibited glycol solutions and electric heat tapes to prevent freezing, especially in low ambient temperatures or during power failures.
  • Refrigerant Circuit Maintenance: Strict adherence to safety precautions for A2L refrigerants, including ensuring adequate ventilation, avoiding ignition sources, safe removal and evacuation procedures (purging with oxygen-free nitrogen), and accurate charging.
  • Pump Modification/Trimming: Instructions for impeller trimming on constant speed pumps to adjust flow and optimize performance, to be performed by qualified personnel.
  • Strainer Maintenance: The PIC6 controls include a feature to remind building owners to clean the strainer by discharging the blow-down valve.