30
30RQS/
RQSY
  
 
039    
045    
050    
060    
    
    
    
090    
100    
120    
140    
160    
 
 
 
If the installation ow rate is below the minimum ow rate, 
there is a risk of excessive fouling.
This is limited by the permitted water heat exchanger 
pressure drop. Also, a minimum water heat exchanger ∆T of 
2.8 K must be guaranteed, which corresponds to a water ow 
rate of 0.09 l/s per kW.
10.6.1 - Minimum water loop volume
The minimum water loop volume, in litres, is given by the 
following formula:
Volume (l) = CAP (kW) x N, where CAP is the nominal 
cooling capacity at nominal operating conditions.
 
 
 (See note)
 
This volume is required to obtain temperature stability and 
precision. To achieve this volume, it may be necessary to add 
a storage tank to the circuit. This tank should be equipped with 
bafes to allow mixing of the uid (water or brine). Please 
refer to the examples below.
For the Buffer Tank Module option, the tank volume must 
be taken into account: 250 litres.
 
Bad Good
Bad Good
10.6.2 - Maximum water loop volume
Units with hydronic module incorporate an expansion tank 
that limits the water loop volume. The table below gives the 
maximum loop volume for pure water or ethylene glycol with 
various concentrations.
30RQS/RQSY 
  1 2 3 1 2 3
 litres    1741 1161 
 l 471 314 157 1373  
 l   130 1135 757 
 l  232 116 1014 676 
 l     562 
30RQS/RQSY 
  1 2 3 1 2 3
 litres    1741 1161 
 l 706 471 235 1373  
 l    1135 757 
 l 522  174 1014 676 
 l 434  145  562 
If the total system volume is higher than the values given 
above, the installer must add another expansion tank, suitable 
for the additional volume. 
Note : Take into account the buffer tank volume (250 litres)
Please refer to the certied dimensional drawings, supplied 
with the unit.
The power supply must conform to the specication on the 
heat pump nameplate. The supply voltage must be within the 
range specied in the electrical data table. For connec-tions 
refer to the wiring diagrams and the certied dimen-sional 
drawings.
WARNING: Operation of the heat pump with an improper 
supply voltage or excessive phase imbalance constitutes 
abuse which will invalidate the Carrier warranty. If the 
phase imbalance exceeds 2% for voltage, or 10% for current, 
contact your local electricity supply at once and ensure that 
the heat pump is not switched on until correc-tive measures 
have been taken.
100 x max. deviation from average voltage 
Average voltage
Example:
On a 400 V - 3 ph - 50 Hz supply, the individual phase voltages 
were measured to be:
AB = 406 V; BC = 399 V; AC = 394 V
Average voltage = (406 + 399 + 394)/3 = 1199/3
    = 399.7 say 400 V
Calculate the maximum deviation from the 400 V average:
(AB) = 406 - 400 = 6