40
Typical control wiring schematics (cont)
LEGEND
NOTES:
1. Compressor and blower motor thermally pro-
tected internally.
2. All wiring to the unit must comply with local
codes.
3. Transformer is wired to 115-V (WHT) lead for
115/1/60 units, 265-V (BRN) lead for 265/1/60
units, 240-V (ORG) lead for 240/1/50 units, or
208-V (RED) lead for 208/1/60 units.
Rewire transformer L1 connection if voltage is
230-1-60 or 220-1-50, insulate unused lead.
4. FP1 thermistor provides freeze protection for
WATER. When using ANTI-FREEZE solutions,
cut JW3 jumper.
5. Refer to LonWorks
®
Installation, Application, and
Operation manual for control wiring to the unit.
Low voltage wiring must be “class 1” and voltage
rated equal to or greater than unit supply
voltage.
6. 24-v alarm signal shown. For dry alarm contact,
cut JW1 jumper. Dry contact will be available
between AL1 and AL2.
7. Transformer secondary ground via Complete C
board standoffs and screws to control box.
(Ground available from top 2 standoffs as
shown.)
*Optional wiring.
AL — Alarm Relay Contacts
BM — Blower Motor
BR — Blower Relay
CAP — Capacitor
CB — Circuit Breaker
CO — Sensor, Condensate Overflow
CR — Compressor Relay
DM — Damper Motor
FP1 — Sensor, Water Coil Freeze Protection
FP2 — Sensor, Air Coil Freeze Protection
HP — High-Pressure Switch
JW1 — Jumper Wire for Alarm
LOC — Loss of Charge Pressure Switch
PB — Power Terminal Block
RVS — Reversing Valve Solenoid
TRANS — Transformer
WV — Water Valve
---------- Field Line Voltage Wiring
Field Low-Voltage Wiring
Option Low-Voltage Wiring
Printed Circuit Trace
Relay/Contactor Coil
Solenoid Coil
Thermistor
Circuit Breaker
Relay Contacts-N.O.
Switch-Temperature
Switch-High Pressure
Switch-Low Pressure
Ground
Wire Nut
Mate-N-Lock
>
>
COMPLETE C
COMPLETE C
PEC
PEC12-18
PEC
a50-8327.eps
50PEC UNIT WITH COMPLETE C AND LON CONTROLLERS