8
falls below 50 F. When return-air temperature is raised
above 55 F the compressor and blower stop.
Override function
— An override function is available for
units operating in occupied/unoccupied mode under the
control of an external timeclock or an energy management
system. A contact closure from the timeclock or energy
management system shorts the NSB and C terminal on the
Deluxe D controller signaling an unoccupied mode.
For units with the unit-mounted thermostat, pressing
override switch (located under control access door) will
override the unoccupied mode and allow the occupied
mode of operation to continue for a period of two hours.
The units with the remote wall-mounted thermostat
require a digital thermostat with the override function. In
unoccupied mode, an accessory relay is energized on the
Deluxe D controller. The NO/NC contacts of the relay can
be used as appropriate input to the digital thermostat to
signal occupied/unoccupied mode. The thermostat selects
cooling/heating set points based on occupied/unoccupied
mode.
PremierLink™ controller is compatible with the Carrier
Comfort Network
®
(CCN) and other building automation
systems (BAS). This control is designed to allow users the
access and ability to change factory-defined settings thus
expanding the function of the standard unit.
LONMark
®
compliant controller contains the factory-
loaded Aquazone™ water source heat pump application
for an interoperable control solution.
WSHP Open multiple protocol controller is a proac-
tive controller capable of communicating BACnet™,
Modbus
®
*, N2, and LON (with a separate card) protocols.
The controller is designed to allow users the access and
ability to change and configure multiple settings and fea-
tures including indoor air quality (IAQ), waterside econo-
mizer controls, etc.
Field-installed accessories
Carrier’s line of Aquazone thermostats (used with
remote thermostat units) are both attractive and multi-
functional, accommodating stand-alone water source heat
pump installations.
Programmable 7-day thermostat
offers 2-stage heat,
2-stage cool, auto changeover, 7-day programmable with
copy command, 4 settings per day, fully electronic, 24 vac,
backlit LCD, keypad lockout, no batteries required,
5-minute compressor protection, NEVERLOST™ memory,
3 security levels, temperature display in degrees F or C.
Programmable 7-day light-activated thermostat
offers
same features as the 7-day programmable thermostat and
includes occupied comfort settings with lights on, unoccu-
pied energy savings with lights off.
Programmable 7-day flush-mount thermostat
offers the
same features as the 7-day programmable thermostat and
includes locking coverplate with tamper proof screws, flush
to wall mount, holiday/vacation programming, set point
limiting, dual point with adjustable deadband, O or B termi-
nal, and optional wall or duct-mounted remote sensor.
Programmable 5-day thermostat
offers 2-stage
heat, 2-stage cool, auto changeover, 5-minute built-
in compressor protection, locking cover included,
temperature display in degrees F or C, keypad lockout,
backlit display, 5-1-1 programming, O or B terminal, dual
set point with adjustable deadband, configurable display,
self-prompting program, 4 settings per day.
Non-programmable thermostat
offers 2 heat stages, 2 cool
stages, auto changeover, 5-minute built in compressor pro-
tection, locking cover included, temperature display in
degrees F or C, keypad lockout, large display, back-lit dis-
play, O or B terminal, dual set point with adjustable dead-
band, backplate with terminals.
Aquazone system control panel includes a pre-
programmed, easy to use, Carrier Comfort Controller set
up for a WSHP system.
• Coordinates, monitors, and controls all WSHP units
and ancillary equipment including cooling towers, boil-
ers, and system pumps.
• 50RLP model nomenclature is used to customize the
panel to control all WSHP system requirements.
• Panel can be ordered to include 2, 4, 6, or 8 stages of
system heat rejection.
• Panel can be ordered to include 2, 4, 6, or 8 stages of
system heat addition.
• Panel can be ordered with unique WSHP zone operation
capabilities for stand alone systems (i.e., non-communicating)
to control 10 or 18 zones of WSHP units.
• Panel can be ordered to control variable frequency cool-
ing tower fan operation.
• System pumping operation can be configured for start/
stop, lead/lag, or variable frequency pump operation.
• Direct digital controls (DDC) compatible using the
Carrier Comfort Network (CCN) and WSHP units utiliz-
ing PremierLink CCN controllers.
UC Open XP loop controller with six stages (2 stages
for heating and 4 stages for cooling) includes:
• Loop temperature alarms
• Two pump single loop flow monitoring with the ability
to manually select the lead pump
• One common alarm signal and indicating light and one
audible alarm
• Loop water temperature sensor test circuit
• Functional test simulation from operator keypad
• Real timeclock, industrial noise ratings
• Loop water temperature control switch
• Loop controller with six stages (2 stages for heating and
4 stages for cooling)
Fire-rated hoses are 2 ft long and have a fixed MPT on
one end and a swivel with an adapter on the other end.
Hose kits are provided with both a supply and return hose
and can be either stainless steel or galvanized. Five sizes
are available (
1
/
2
,
3
/
4
, 1, 1
1
/
4
, 1
1
/
2
in.).
Ball valves (brass body) used for shutoff and balancing
water flow. Available with memory, memory stop, and
pressure temperature ports. UL-listed brass body, ball and
stem type with Teflon† seats and seals. Five sizes are avail-
able (
1
/
2
,
3
/
4
, 1, 1
1
/
4
, 1
1
/
2
in.).
Y strainers (bronze body) are “Y” type strainers with a
brass cap. Maximum operating pressure rating of
450 psi. Strainer screen made of stainless steel. Available
with blow down valves. Five sizes are available (
1
/
2
,
3
/
4
, 1,
1
1
/
4
, 1
1
/
2
in.).
Options and accessories (cont)
*Registered trademark of Schneider Electric.
†Teflon is a trademark of E. I. du Pont de Nemours and Company.