Outdoor Fan Error F5
38MARBQ09~36AA3 Outdoor Units
Troubleshooting:
Troubleshooting:
Error may only displayed every 3 minutes, during this time you may 
see either “normal display” or “88” on indoor unit or wired control.
When the indoor fan speed is too slow (300 RPM 
or less) for 3 minutes or more, the unit stops and 
the LED displays the Error Code for 30 seconds. 
Then retries until locks out.
Free up, replace any broken 
parts so fan spins freely
Shut OFF the power supply. 
Rotate the Indoor fan by hand.       
Does the fan rotate freely?
No
Yes
Replace fan motor and 
Control Box Assembly   
or Main PCB
Dr. Smart 
Display
For Instructions on 
how to change 
Control Box or Main 
PCB, see Table of 
Contents in beginning 
of this guide
!
Attention:
When replacing Main PCB ONLY,          
you will need Conductive Grease.
Carrier Factory Authorized Parts 
38AQ680001 Conductive Grease
18K ONLY - Ohm out reactor, remove wires first. 
Reading should be close to Zero between 
terminals. Also check each connection to ground, 
this should be open. If not replace.
9K, 12K (120 & 220-Volt) 18K, 
Replace Entire Control Box Assembly
24K, 30K, 36K
Replace Main PCB ONLY 
If after parts replacement, F5 is 
still displayed, contact your local 
CE Technical Support Rep.
Follow the “1st Steps for DLS Troubleshooting” 
in the beginning of this guide, if you have an 
active error, procedure below.