Heating & Cooling Compensation
Examples of how the Cooling Compensation setting moves
the entire swing up or down.
Default F7 for AHB & PHA High Wall Units:
If you change F2 to -2C, the entire swing moves down 2C(3.6F)
Cool Mode 40MAHB/40MPHA
619AHB/619PHA
7.2°(4C) Swing at Control Sensor
+0.9°(0.5C)
73°(72.5°)(22.5C)
65°(65.3°)(18.5C)
-6.3°(3.5C)
T1 Return Sensor & Set
Point 72°(71.6)(22C)
F2 = 0C
+0.9°(0.5C)
69°(68.9°)(20.5C)
62°(61.7°)(16.5C)
Cool Mode
-6.3°(3.5C)
7.2°(4C) Swing at Return Air Sensor
T1 Return Sensor
68°(20C)
F7 = -2C
72°(71.6°)(22C)
Set Point
Continued on next page