Carrier Bryant Payne day and night 585A/YAC - Heating System Startup and Tuning; Gas Input and Burner Settings

Carrier Bryant Payne day and night 585A/YAC
14 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SINGLE-STAGE
HEAT
a
COOL-MANUAL
CHANGEOVER
--
FIELD
LOW-VOLTAGE
WIRING
———
FIELD
HIGH-VOLTAGE
WIRING
-
FACTORY
LOW-VOLTAGE
WIRING
A76313
——
FACTORY
HIGH-VOLTAGE
WIRING
Figure
11
—High-
&
Low-Voltage
Connections
230-V
OPERATION
BRNt
YELfe
redL
BLK^
ORN^
4
3
2
1
C
MOTOR
LEADS
molex
PLUG
CONNECTOR
208-V
OPERATION
A
BRNt:
4
3
2
R1
Kf-
1
C
\
MOTOR
LEADS
A76314
MOLEX
PLUG
CONNECTOR
Figure
1
2
—Evaporator
Motor
Molex
Plug
Connections
for
018050-Size
Unit
3.
Make
certain
gas
supply
has
been
purged
and
all
gas
piping
checked.
WARNING:
Do
not
purge
into
the
combustion
chamber.
Do
not
use
a
match
or
other
open
flame
to
check
for
leakage.
4.
Check
to
be
sure
all
wiring
connections,
including
facto¬
ry
connections,
have
been
completed
and
are
tight.
5.
Inspect
all
supply
ducts
and
grilles
to
be
sure
they
are
adjusted
properly.
6.
Check
to
be
sure
air
filters
are
in
place.
Vll.
HEATING
STARTUP
AND
ADJUSTMENTS
CAUTION:
Complete
the
steps
in
Section
VI
before
starting
unit.
CAUTION:
Do
not
jumper
any
safety
devices
when
operat¬
ing
unit.
Follow
the
instructions
on
the
unit
rating
plate
for
starting
the
heating
section.
NOTE:
On
all
3-phase
units,
make
certain
blower
rotates
in
same
direction
as
shown
on
arrow
rotation
label
attached
to
blower.
If
blower
rotates
in
opposite
direction,
reverse
any
two
blower
motor
leads
or
any
two
line-voltage
leads
for
cor¬
rect
rotation.
A.
Adjusting
Gas
Input
(Natural
Gas
Furnace)
The
gas
input
should
agree
with
that
shown
on
the
unit
rat¬
ing
plate.
The
burners
are
equipped
with
fixed
orifices.
NOTE:
The
rating
shown
on
the
rating
plate
is
for
altitudes
up
to
2000
feet
above
sea
level.
For
elevations
above
2000
feet,
reduce
ratings
4%
for
each
1000
feet
above
sea
level.
The
main
burner
orifices
must
be
changed
to
a
smaller
size.
One
of
the
two
following
methods
may
be
used
to
adjust
the
input
on
a
natural
gas
unit.
1.
Measuring
Gas
Flow
at
Meter
All
other
gas
appliances
must
be
turned
off
when
measuring
gas
flow
at
meter
to
check
the
input.
Proceed
as
follows:
a.
Determine
number
of
seconds
for
gas
meter
test
dial
to
make
one
revolution.
b.
Divide
3600
by
number
of
seconds
in
step
a,
c.
Multiply
result
of
Step
b
by
the
number
of
cubic
feet
shown
for
one
revolution
of
test
dial.
This
gives
cubic
feet
of
gas
flow
per
hour.
d.
Multiply
result
to
Step
c
by
Btu
heating
value
of
gas.
Consult
local
utility
for
heating
value
of
gas.
This
is
the
total
measured
input
in
Btuh.
Compare
this
value
with
input
rating
shown
on
the
unit
rating
plate.
Example:
Suppose
the
size
of
test
dial
is
1
cubic
foot;
it
takes
30
seconds
to
complete
one
revolution;
heating
value
of
gas
1050
Btu
per
cubic
foot.
Proceed
as
follows:
a.
30
seconds
to
complete
one
revolution.
b.
3600
divided
by
30
equals
120.
c.
120
times
1
equals
120
cubic
feet
of
gas
flow
per
hour.
d.
120
times
1050
equals
126,000-Btuh
input.