EasyManua.ls Logo

Carrier Bryant Payne day and night 585A/YAC - Low-Voltage Wiring; Unit Startup Preparation; Pre-Startup Inspection and Checks

Carrier Bryant Payne day and night 585A/YAC
14 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
s
HINGED
RETURN
AIR
GRILLE
\
*
5
WEATHERPROOF
FLASHING
PARALLEL
FLOW
TRANSITION
AND
FI
L
TER
P
LENUM
(FIELD-
SUPPLIED)
7
FILTER
ACCESS
PANEL
(FIELD-SUPPLIED)
HOUSE
FLOOR
SLAB
Figure
10—Typical
Ground
Level.lnstallation
Through
Single
Closet
A7631
2
See
Figure
2
for
location
of
panel
and
hole.
NOTE:
A
suitable
conduit
fitting
should
be
mounted
to
the
unit
at
this
hole.
NOTE:
The
fused
disconnect
may
be
mounted
directly
on
the
control
corner
panel.
Tb
mount
the
disconnect
on
this
panel,
align
one
of
the
disconnect
box
knockouts
with
the
unit
high-voltage
inlet
hole
and
secure
the
box
to
the
panel.
Route
the
wiring
from
the
disconnect
through
the
aligned
knockout
and
unit
inlet.
WARNING:
Ensure
that
the
drill
does
not
damage
any
com¬
ponents
when
drilling
through
the
panel.
2.
Run
high-voltage
leads
to
unit
control
box
and
connect
leads
to
contactor.
See
unit
wiring
label
and
Figure
11.
NOTE:
On
3-phase
units,
the
third
power
lead
is
connected
to
the
brown
high-voltage
pigtail
lead.
See
unit
wiring
label
and
Figure
11.
When
the
018050-size
unit
is
to
be
operated
at
208
volts,
it
must
be
rewired
at
the
Molex
plug
connector
of
both
the
evaporator
and
condenser
motor,
and
at
the
unit
trans¬
former.
WARNING:
Make
sure
the
power
supply
to
the
unit
is
switched
OFF
before
making
any
wiring
changes.
NOTE:
Molex
plug
connector
leads
may
be
disconnected
by
inserting
a
small
screwdriver,
or
similar
bladed
tool,
into
the
connector
and
depressing
the
catch
on
the
terminal.
When
inserting
a
lead,
be
sure
the
catch
on
the
terminal
is
seated
into
the
connector.
The
018050-size
unit
evaporator
motor
leads
are
wired
at
the
connector
as
shown
in
Figure
12.
The
yellow
and
orange
leads
are
interchanged
when
operating
at
208
volts.
See
unit
wiring
label.
See
Figure
7
for
connector
location.
The
018050-size
unit
condenser
motor
must
have
the
red
and
black
motor
leads
changed
at
the
plug
connector
when
operating
at
208
volts.
See
the
unit
wiring
label.
On
the
018050-size
unit,
the
orange
lead
running
to
the
primary
side
of
the
unit
transformer
must
be
connected
to
the
red
transformer
tap
when
operating
at
208
volts.
See
the
unit
wiring
label.
B.
Low-Voltage
Connections
CAUTION:
When
thermostat
leads
are
run
in
the
satt;
con¬
duit
with
the
high-voltage
leads,
they
must
be
insulated
for
the
highest
voltage"contained
with
the
conduit.
ijgs
If
the
low-voltage
leads
from
the
thermostat
are
run
sepa¬
rately,
enter
the
unit
through
the
grommeted
hole
provided
in
the
control
comer
panel.
See
Figure
2
for
the
hole
loca¬
tion.
Connect
the
low-voltage
thermostat
leads
to
the
flagged
pigtail
leads
that
run
through
a
hole
in
the
bottom
of
the
unit
control
box.
See
Figures
7
and
11.
NOTE:
Connect
thermostat
to
unit
using
NO.
18
AWG
“col¬
or-coded”
insulated
wires.
If
thermostat
is
located
more
than
50
feet
from
unit,
use
No.
16
AWG
wire.
Use
thermostats
and
subbases
shown
in
Figure
11.
Set
heat
anticipator
to
0.8
amps.
VI.
PREPARING
UNIT
FOR
STARTUP
Proceed
as
follows
to
prepare
the
unit
for
startup:
1.
Remove
all
service
access
panels
and
check
for
shipping
damages,
such
as
broken
lines,
loose
parts,
disconnected
wires,
etc.
2.
Read
and
follow
instructions
on
all
WARNING,
CAU¬
TION,
AND
INFORMATION
labels
and
tags
attached
to
unit;
such
as
motor
rotation
labels,
blower
rotation
labels,
and
vent
instruction
tag.
-
1
-

Related product manuals