SELECTING INSTALLATION LOCATION OF SIDE DISCHARGE - OUTDOOR UNIT
9.3 Minimum Clearances When Selecting Installation Location for Single Outdoor Unit Installation
Minimum Clearances When Selecting Installation Location for Serial Installation
of More Than One Outdoor Unit
Select installation location which allows the minimum clearances shown in the figures for free
air circulation and easy accessibility for service and maintenance :
The front of outdoor unit ( air outlet )
should be away from any obstacle by 500 mm or more to ensure free air circulation.
The back of outdoor unit ( air inlet )
should be away from any obstacle by 160 mm or more. This distance is built in the design of wall support
to ensure free air circulation.
The left side of outdoor unit
should by away from any obstacle by 400 mm or more to ensure easy access to refrigerant and electrical
connections.
The right side of outdoor unit ( air inlet )
should be away from any obstacle by 250 mm or more to ensure free air circulation.
The top side of outdoor unit
should be away from any obstacle by 400 mm or more to ensure easy access to the electrical
components, motor and fan.