CONNECTING ELECTRICAL WIRING
19-5 Ducted Split Systems – High Static Pressure
Cool Only – 380-420V / 3 Ph / 50Hz
53KDHT60N-518 53KDHT72N-518 53KDHT84N-518 53KDHT90N-518
Caution – Field Electrical Wiring
NOTES
(1) Connect the power supply to the outdoor unit and then get the power required for the indoor unit from the outdoor unit.
(2) Refer to wiring diagrams and stickers-caution field electrical wiring sticked inside the outdoor and indoor units.
Outdoor Units
38KDHT60N-518
38KDHT72N-518
38KDHT84N-518
38KDHT90N-518
Power supply:
Single-Phase 220~240V / 1Ph / 50Hz
Use 3-core cable 3 x 1 m
2
Power supply:
Three-Phase 380~420V / 3Ph / 50Hz
Use 5-core cable 5 x 2.5 m
2
Use 3-core cable 3 x 0.2 m
2
Indoor Units
42KDHT60N-718
42KDHT72N-718
42KDHT84N-718
42KDHT90N-718