EasyManua.ls Logo

Carrier ComfortLink 30GXN - Comfort Link Compressor Protection (CCP) Board; Outputs; Inputs

Carrier ComfortLink 30GXN
140 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7
Comfort
Link™ Compressor Protection (CCP)
Board
One CCP board controls up to 2 compressors.
The CCP provides the following functions:
compressor main contactor control
Wye-Delta contactor transition
compressor ground current protection
motor temperature reading
high-pressure protection
reverse rotation protection
current imbalance protection
compressor oil solenoid control
motor cooling solenoid control
LEN communications
starting and running overcurrent protection
The CCP has the following 4 output relays and 3 inputs:
OUTPUTS:
compressor contactor
compressor oil solenoid
compressor motor cooling solenoid
Wye-Delta transition relay
INPUTS:
motor temperature
three-phase current
high-pressure switch
A diagram of the CCP board is shown in Fig. 4. One CCP
board is installed on 30GXN,R080-178 and 30HXA,C076-186
units and two CCP boards are installed on 30GXN,R204-350
and 30HXA,C206-271 units. The address for each CCP board
is set using DIP (dual in-line package) switches. For CCP1
(compressor A1 and B1), DIP switch 1 should be set to ‘L
(‘On’ position for LEN communication). Switches 2, 3 and 4
should be set to ‘0’ (“OFF” position). For CCP2 (compressor
A2 for 30GXN,R204-268 and 30HXA,C206-271 and com-
pressor B2 for 30GXN,R281-350), switch 1 should be set to
‘L and switches 3 and 4 should be set to ‘1’ (“ON” position).
Switch 2 should be set to ‘0’ (“OFF” position). See Table 4 for
CCP board connections. The CCP has a reset button located
between the DIP switch and the J10 connector.
Each compressor's MTA (must trip amps) setting is commu-
nicated to the MBB during the initialization period. See Table 5
for DIP switch settings.
L
1
1
S
SW1
SW2
SW3 SW4
00
12
3
4
5
1
2
3
1
2
3
4
5
4
3
2
1
3
2
1
3
2
1
1
2
3
4
3
2
1
8
1
8
1
GREEN LED
COMP A1/A2
MTA HEADER
RED LED
COMP B1/B2
MTA HEADER
J1
J7
J6
J9
J8
J4
J5
J2
J3
J10
J11
RESET
BUTTON
DIP
SWITCH
1
2
3
4
1
2
3
1
2
3
1
2
3
0
0
S
L
11
ON
ON
LEGEND
NOTES:
1. The red LED blinks continuously when the mod-
ule is operating properly.
2. The green LED blinks continuously when com-
municating properly with MBB.
3. On all connectors, pin 1 is identified by a ”.
4. Control power to CCP board must be off before
making any changes to DIP switch settings.
5. DIP switch 2 disables compressor ground current
protection, ON = DISABLE.
LED Light-Emitting Diode
MBB Main Base Board
MTA Must Trip Amps
L—LEN (Local Equipment Network)
S—SIO (Sensor Input/Output)
Fig. 4
Comfort
Link™ Compressor Protection (CCP) Board

Table of Contents

Related product manuals