122
APPENDIX G (cont)
DUALCHIL: Maintenance Display
LOADFACT: Maintenance Display
MISCDATA: Maintenance Display
OCCDEFM: Occupancy Maintenance Display
DESCRIPTION STATUS UNITS POINT
Dual Chiller Link Good? Yes/No DC_LINK
Master Chiller Role STAND ALONE, Lead Chiller, Lag Chiller MC_ROLE
Slave Chiller Role STAND ALONE, Lead Chiller, Lag Chiller SC_ROLE
Lead Chiller Ctrl Point snnn.n dF LEAD_CP
Lag Chiller Ctrl Point snnn.n dF LAG_CP
Control Point snnn.n dF CTRL_PNT
Cool Entering Fluid-Slave snnn.n dF COOLEWTS
Cool Leaving Fluid-Slave snnn.n dF COOLLWTS
Cooler Entering Fluid snnn.n dF COOL_EWT
Cooler Leaving Fluid snnn.n dF COOL_LWT
Lead/Lag Leaving Fluid snnn.n dF DUAL_LWT
Percent Avail.Capacity 0-100 % CAP_A
Percent Avail.Cap.Slave 0-100 % CAP_A_S
Lag Start Delay Time hh:mm LAGDELAY
Load/Unload Factor snnn.n SMZ
Load/Unload Factor-Slave snnn.n SMZSLAVE
Lead SMZ Clear Commanded Yes/No LEADSMZC
Lag- SMZ Clear Commanded Ye s/ N o L AG _ SM Z C
Lag Commanded Off? Yes/No LAG_OFF
Dual Chill Lead CapLimit 0-100 % DCLDCAPL
Dual Chill Lag CapLimit 0-100 % DCLGCAPL
DESCRIPTION STATUS UNITS POINT
CAPACITY CONTROL
Load/Unload Factor snnn.n % SMZ
Control Point snnn.n °F CTRL_PNT
Leaving Fluid Temp snnn.n °FLWT
Calculated Z factor n.n Z_CALC
Capacity Trans. State n CAP_TRAN
DESCRIPTION STATUS UNITS POINT
MISCELLANEOUS
Options Temp 1, EXV AN2 snnn.n °FOPT_TMP1
Options Temp 2, EXV AN1 snnn.n °FOPT_TMP2
Options Temp 3, SCB AN9 snnn.n °FOPT_TMP3
Options Temp 4, SCB AN10 snnn.n °FOPT_TMP4
Options Current 1 nn.n ma OPT_CUR1
Options Current 2 nn.n ma OPT_CUR2
Pumpout Failure Count, A nnn PFAIL_A
Pumpout Failure Count, B nnn PFAIL_B
HXC Brine Config Lock No/Yes BRN_LOCK
DESCRIPTION STATUS POINT
Current Mode (1=Occup.) 0,1 MODE
Current Occup. Period # 0-8 PER-NO
Timed-Override in Effect Yes/No OVERLAST
Time-Override Duration 0-4 hours OVR_HRS
Current Occupied Time hh:mm STRTTIME
Current Unoccupied Time hh:mm ENDTIME
Next Occupied Day NXTOCDAY
Next Occupied Time hh:mm NXTOCTIM
Next Unoccupied Day NXTUNDAY
Next Unoccupied Time hh:mm NXTUNTIM
Previous Unoccupied Day PRVUNDAY
Previous Unoccupied Time hh:mm PRVUNTIM