17
 
MULTI-SPEED FAN SUPPORT
The economizer controller supports connection to 2 and 3-speed 
fans. When the unit is equipped with a multi-speed fan, the damp
-
er responds to multiple fan speeds via multiple minimum positions 
(MIN POS) to keep minimum airflow. Refer to Tables 
13-15.
 
If DCV (demand controlled ventilation) is enabled, then each fan 
speed corresponds to two damper position ventilation setpoints 
(VENT MIN, VENT MAX), e.g., Pos L corresponds to 
2VENTMIN L... 2VENTMAX L. Refer to Table 
16.
If CO
2
 sensor is connected but DCV is disabled, then each fan 
speed corresponds to one minimum damper position ventilation 
setpoint. Refer to Table 
17.
 
Table 11 — 1 and 2-Stage Cooling Stage I/O Logic 
ECONOMIZER 
CONDITION MET
Y1 Y2
COOLING 
STAGE 1
COOLING 
STAGE 2
NO On On On On
NO On Off On Off
NO Off Off Off Off
YES On On On On/Off
a
a. If OAT  MAT setpoint (3MAT SET), then Relay 2 is always OFF to disable 
Cooling Stage 2. Otherwise, if both stages of cooling (Y1 and Y2) are ON for 
more than a set time (15 minutes by default), Y2 remains ON, and the OAT is 
higher than MAT setpoint, then Relay 2 energizes to allow Y2 pass-through to 
enable Cooling Stage 2. To change the set time, configure 3STG3 DLY as de-
sired. See Advanced Settings page 27 for more details of 3STG3 DLY.
YES On Off Off Off
YES Off Off Off Off
Table 12 — 2 and 3-Stage Cooling Stage I/O Logic 
ECONOMIZER 
CONDITION 
MET
Y1 Y2 Y3
COOLING 
STAGE 1
COOLING 
STAGE 2
COOLING 
STAGE 3
NO On On On On On On
NO On On Off On On Off
NO On Off Off On Off Off
NO Off Off Off Off Off Off
YES On On On On On On/Off
a
a. If OAT  MAT setpoint, then Relay 3 is always OFF to disable Cooling Stage 3. 
Otherwise, if all cooling stages (Y1, Y2 and Y3) are ON for more than a set time 
(15 minutes by default), Y3 remains ON, and the OAT is higher than MAT set-
point, then Relay 3 energizes to allow AUX1/AUX2 pass-through to enable 
Cooling Stage 3. To change the set time, configure 3STG3 DLY as desired. See 
Advanced Settings page 27 for more details of 3STG3 DLY.
YES On On Off On On/Off Off
YES On Off Off Off Off Off
YES Off Off Off Off Off Off
IMPORTANT: The economizer controller can tolerate thermo-
stat wiring mismatch, e.g. Thermostat Y1  Economizer Y2-In, 
Thermostat Y2  Economizer Y1-In. The handling logic is 
Stage =Y1I + Y2I + Y3I. For example, Y1O =1 if Stage > =1, 
Y2O =1 if Stage > = 2, Y3O=1 if Stage=3.
Table 13 — Damper MIN POS for 2-Speed Fan
a
 
a. A multi-speed fan is not controlled by the economizer controller, but an external 
logic board.
Y1 Y2 W1 or O/B Spd L Spd H Pos L Pos H
X —— X—X—
X X— —X—X
 — —X —X—X
LEGEND
Pos L — Damper MIN POS for Low-Speed Fan
Pos H — Damper MIN POS for High-Speed Fan
Spd L — Low Speed (Fan)
Spd H — High Speed (Fan)
Table 14 — Different Fan Speeds with Different 
Configured Outputs
a
 
a. If a single-speed fan connects to the Controller, then it opens directly on the call 
of cooling/heating. The damper position is Pos H.
FAN 
TYPE
1-SPEED 
COOLING
b
b. Configured by Y1O, Y2O, or Y3O.
2-STAGE 
COOLING
b
3-STAGE 
COOLING
b
1-SPEED 
FAN
c
c. Configured by 6FAN.
• Spd H) 
(regardless of 
cooling 
demand, 
OCC=Yes)
• Spd H) 
(regardless of 
cooling 
demand, 
OCC=Yes)
• Spd H 
(regardless of 
cooling demand, 
OCC=Yes)
2-SPEED 
FAN
c
• Spd L 
(0 or 1 cooling 
demand) 
• Spd H 
(2 cooling 
demands)
• Spd L
 (0 or 1 cooling 
demand)
• Spd H3) 
(2 cooling 
demands)
• Spd L 
(0 or 1 cooling 
demand)
•  Spd H 
(2 or 3 cooling 
demands)
LEGEND
Spd L — Low Speed (Fan)
Spd H — High Speed (Fan)
Table 15 — Different Damper Minimum Positions with 
Different Configured Outputs 
FAN 
TYPE
1-SPEED 
COOLING
a
a. Configured by Y1O, Y2O, or Y3O.
2-STAGE 
COOLING
b
3-STAGE 
COOLING
b
1-SPEED 
FAN
b
b. Configured by 6FAN.
•Pos H 
(regardless of 
cooling 
demand, 
OCC=Yes)
•Pos H 
(regardless of 
cooling 
demand, 
OCC=Yes)
•Pos H 
(regardless of 
cooling 
demand, 
OCC=Yes)
2-SPEED 
FAN
b
•Pos H 
(regardless of 
cooling 
demand, 
OCC=Yes)
• Pos L 
(0 or 1 cooling 
demand)
•Pos H
(2 cooling 
demands)
• Pos L4
(0 or 1 cooling 
demand)
• Pos H 
(2 or 3 cooling 
demands)
LEGEND
Pos L — Damper MIN POS for Low-Speed Fan
Pos H — Damper MIN POS for High-Speed Fan