F80CTL and G80CTL: Installation, Start–Up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
32
NOT forget to return setup switch to OFF position and remove jumper
upon completion of testing. 
c. This furnace is capable of automatically providing proper airflow
to  maintain  the  temperature  rise  within  the  range  specified  on
furnace  rating  plate.  If  temperature  rise  is  outside  this  range,
proceed as follows:
(1.) Check gas input for low- and high-heat operation.
(2.) Check derate for altitude if applicable.
(3.) Check all return and supply ducts for excessive restrictions 
causing static pressure greater than 0.5-In. W.C.
(4.) Ensure setup switch SW1-4 (Comfort/Efficiency) is in 
OFF=Efficiency position when a bypass humidifier is used, 
see Fig. 32 for switch location.)
(5.) Make sure proper model plug is installed.
d. Remove  thermostat  jumpers  and  release  blower  access  door
switch.
e. Repeat  Steps  a  through  c  as  required  to  adjust  for  high  heat
temperature rise.
f. When  correct  high  heat  input  rate  and  temperature  rise  is
achieved, turn gas valve ON/OFF switch to OFF.
g. Release blower access door switch.
h. Remove manometer or similar device from gas valve.
i. Re-install manifold pressure tap plug in gas valve, see Fig. 21. 
j. Remove thermostat jumper wire from furnace control board.
k. Turn gas valve ON/OFF switch to ON.
l. Proceed  to  Step  7,  “Set  Blower  Off  Delay”  before  installing
blower access door. 
7. Set Blower Off Delay
a. Remove blower access door if installed.
b. Turn Dip switch SW-7 or SW-8 ON or OFF for desired blower
off delay, see Table 12, Table 14, Fig. 32, and Fig. 53.
 
8. Set thermostat heat anticipator.
a. Mechanical thermostat. Set thermostat heat anticipator to match
the  amp.  draw  of  the  electrical  components  in  the  R-W/W1
circuit. Accurate amp. draw readings can be obtained at the wires
normally  connected  to  thermostat  subbase  terminals, R  and W.
The  thermostat  anticipator  should  NOT  be  in  the  circuit  while
measuring current.
(1.) Set SW1-2 switch on furnace control board to ON.
(2.) Remove thermostat from subbase or from wall.
(3.) Connect an amp. meter across the R and W subbase 
terminals or R and W wires at wall, see Fig. 48. 
(4.) Record amp. draw across terminals when furnace is in low 
heat and after blower starts.
(5.) Set heat anticipator on thermostat per thermostat 
instructions and install on subbase or wall.
(6.)  Turn SW1-2 switch OFF.
(7.) Install blower access door.
b. Electronic thermostat: Set cycle rate for 3 cycles per hr.
9. Set  Airflow  for  Air  Conditioning  -Single  Stage  and  High  Stage
Cooling 
The  ECM  blower can  be adjusted for a  range of airflow for  Low
Speed  or  High  Speed  cooling.  See  Table 4-Air  Delivery  -  CFM
(With Filter). Depending on the model size, the cooling airflow can
be  adjusted  from  1.5  to  6  tons  based  on  350  CFM/ton.  Refer  to
Table 13.
The cooling airflow is adjusted by turning Setup switches SW2-1,
SW2-2 and SW2-3 either ON or OFF. Select the required airflow,
see Fig. 14. Fig. 14 is based on 350 CFM per ton. For airflow at 400
CFM  per  ton,  turn  Setup  SW1-5  ON,  see  Table 12,  Table 14,
Fig. 32, and Fig. 53.
A96316
Fig. 48 – Amp. Draw Check with Ammeter
NOTE: 5.5 ton airflow will truncate at 2200 cfm on applicable models.
For a complete explanation of cooling airflow, refer to the section titled
“Sequence of Operation.”
Set Airflow For Continuous Fan/Low Speed Cooling Airflow The ECM 
blower motor can be adjusted for continuous fan speeds different than 
heating or cooling fan speed. See Table 4 - Air Delivery - CFM (With 
Filter). Select the required continuous fan airflow, see Fig. 14.
The continuous fan speed is also the switch setting for low speed cooling 
when furnace is used with a 2-speed cooling unit. Adjust the Continuous 
Fan CFM to match the airflow required for low speed cooling. Select the 
required airflow, see Fig. 50. For airflow at 400 CFM per ton, turn Setup 
SW1-5 ON, see Fig. 14. The airflow selected for low speed cooling will 
also be the airflow used for continuous fan. 
Check Safety Controls
The flame sensor, gas valve, and pressure switch were all checked in the
Start-up procedure section as part of normal operation. 
1. Check Main Limit Switch 
This  control  shuts  off  combustion  system  and  energizes
air-circulating  blower  motor,  if  furnace  overheats.  By  using  this
WARNING
!
FIRE HAZARD
Failure  to  follow  this  warning  could  result  in  personal  injury,  death,
and/or property damage. 
Reinstall manifold pressure tap plug in gas valve to prevent gas leak.
CAUTION
!
FURNACE OVERHEATING HAZARD
Failure to follow this caution may result in reduced furnace life. 
Recheck  temperature  rise.  It  must  be  within  limits  specified  on  the
rating plate. Recommended operation is at the mid-point of rise range
or slightly above. 
Table 12 – Blower Off Delay Setup Switch 
DESIRED HEATING MODE
BLOWER OFF DELAY (SEC.) 
SETUP SWITCH
(SW-7 AND -8)
POSITION 
SW1-7  SW1-8 
90  OFF  OFF 
120  ON  OFF 
150  OFF  ON 
180  ON  ON 
R Y W G
10 TURNS
THERMOSTAT SUBBASE
TERMINALS WITH
THERMOSTAT REMOVED
(ANITICIPATOR, CLOCK, ETC.,
MUST BE OUT OF CIRCUIT.)
HOOK-AROUND
AMMETER
EXAMPLE:
5.0 AMPS ON AMMETER
10 TURNS AROUND JAWS
 =  
0.5 AMPS FOR THERMOSTAT
     ANTICIPATOR SETTING
FROM UNIT 24-V
CONTROL TERMINALS