Troubleshooting
i-Vu® CCN Router CARRIER CORPORATION ©2021
Installation Guide All rights reserved
9
Other LED's show the status of certain functions.
To replace the i-Vu® CCN Router's battery
The i-Vu® CCN Router's 10-year Lithium CR123A battery retains the following data for a maximum of 720 hours
during power outages: time, control programs, editable properties, schedules, and trends.
To conserve battery life, you can set the driver to turn off battery backup after a specified number of days and
depend on the archive function to restore data when the power returns.
A low battery is indicated by the Battery low LED or a low battery alarm in the i-Vu® application. You can purchase
replacement batteries from any retailer that sells a CR-123A battery.
1 Verify that the i-Vu® CCN Router's power is on.
2 Using a small flathead screwdriver, pry up each side of the black battery clip until it is free and you can
remove it.
3 Remove the battery from the controller, making note of the battery's polarity.
4 Insert the new battery into the controller, matching the polarity of the battery you removed.
5 Push the black clip back onto the battery until you hear both sides click in place.
6 Download the i-Vu® CCN Router.