Transfer the Refrigerant from Machine to Storage Tank
1.
Equalize refrigerant pressure.
a.
Valve positions:
b.
Slowly open valve 5 and liquid line valve 7 to allow liquid refrigerant to drain by gravity
into the storage tank.
2.
Transfer the remaining liquid.
a.
Turn off pumpout condenser water. Place valves in the following positions:
Valve
1a 1b 2 3 4 5 6 7 8 11 12 13 14
Condition
CCCCC
Valve
1a 1b 2 3 4 5 6 7 8 11 12 13 14
Condition
CC C
Valve
1a 1b 2 3 4 5 6 7 8 11 12 13 14
Condition
CC C