EasyManua.ls Logo

Carrier PC211 - Lead;Lag Control

Carrier PC211
392 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Lead/Lag Control
Note:
Lead/lag control is only available on machines with PSIO Software Version 09 or higher.
Lead/lag is a control system process that automatically starts and stops a lag or second
chiller in a 2-chiller water system. Refer to Figure 16 and Figure 17 for menu, table, and screen
selection information. On machines that have PSIO software with Lead/Lag capability, it is
possible to utilize the PIC controls to perform the lead/lag function on 2 machines. A third
machine can be added to the lead/lag system as a standby chiller to start up in case the lead or
lag chiller in the system has shut down during an alarm condition and additional cooling is
required.
Note:
Lead/lag configuration is viewed and edited under Lead/Lag in the Equipment Configura-
tion table (located in the Service menu). Lead/lag status during machine operation is
viewed in the MAINT04 table in the Control Algorithm Status table. See Table 2.
Lead/Lag System Requirements:
all machines must have PSIO software capable of performing the lead/lag function
water pumps MUST be energized from the PIC controls
water flows should be constant
CCN Time Schedules for all machines must be identical