6
ELECTRIC HEATERS
ORDERING NO.
NOMINAL
CAPACITY (kW
@ 240 or 480
VOLTS)
USED WITH SIZES
024 030 036 042 048 060
208/230 --- SINGLE PHAS E --- 60 HZ
CPHEATER052A00 5.0 X X X
CPHEATER064A00 5.0 X X X
CPHEATER070A00 7.2 X X X X X X
CPHEATER050A00 10.0 X X X X X X
CPHEATER066A00 15.0 X X X X X
CPHEATER054A00 20.0 X X X
208/230 --- THREE PHASE --- 60 HZ
CPHEATER055A00 5.0 X X X X X
CPHEATER056A00 10.0 X X X
CPHEATER068A00 10.0 X X
CPHEATER058A00 15.0 X X X X X
CPHEATER059A01 20.0 X X X
4 6 0 --- T H R E E P H AS E --- 6 0 H Z
CPHEATER060A00 5.0 X X X X
CPHEATER061A00 10.0 X X X X
CPHEATER062A00 15.0 X X X X
CPHEATER063A00 20.0 X X X
NOTE: Electric heaters ar e rated at 240v. Refer to Multiplication Factors table for other voltages.
X = Approved combination
Minimum Airflow for Reliable Electric Heater Operation (cfm)
UNIT--50VT 024 030 036 042 048 060
AIRFLOW 800 1025 1250 1400 1710 1800