PG92MSA: Installation, Start-up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
18
hung  from  floor  joists,  rafters  or  trusses  or  installed  on  a
non-combustible platform, blocks, bricks or pad. 
Supply Air Connections 
For a furnace not equipped with a cooling coil, the outlet duct shall be
provided  with  a  removable  access  panel.  This  opening  shall  be
accessible when the furnace is installed and shall be of such a size that
the  heat  exchanger  can  be  viewed  for  possible  openings  using  light
assistance or a  probe  can  be  inserted for sampling  the  air stream. The
cover attachment shall prevent leaks. 
Connect  supply-air  duct  to  flanges  on  furnace  supply-air  outlet.  Bend
flange upward to 90° with wide duct pliers. See Fig. 20. The supply-air
duct  must  be  connected  to  ONLY  the  furnace  supply-outlet-air  duct
flanges or air conditioning coil casing (when used). DO NOT cut main
furnace  casing  side  to  attach  supply  air  duct,  humidifier,  or  other
accessories. All  supply-side  accessories  MUST  be  connected  to  duct
external to furnace main casing. 
Return Air Connections 
The return-air duct can only be connected to bottom of the furnace. The
sides of casing cannot be used for return air connection. See Fig. 23.
Bottom Return Air Inlet 
These furnaces are shipped with bottom closure panel installed in bottom
return-air opening. Remove and discard  this panel when bottom return
air is used. To remove bottom closure panel, see Fig. 24.
Side Return Air Inlet 
These furnaces are shipped with bottom closure panel installed in bottom
return-air  opening. This  panel  MUST  be in  place  when side  return air
inlet(s) are used without a bottom return air inlet.
Not all horizontal furnaces are approved for side return air connections
See Fig. 23. Where required by code, seal bottom closure to furnace with
tape, mastic, or other durable sealing method.
CAUTION
!
FURNACE RELIABILITY HAZARD
Failure to follow this caution may result in unit component damage.
Return  air  connections  to  either  side  of  the  furnace  in  the  horizontal
position  can  result  in  nuisance  limit  switch  tripping.  Use  only  the
factory bottom opening of the furnace for the return air connection.
Table 6 – Opening Dimensions - In. (mm)
FURNACE 
CASING WIDTH
IN. (mm) 
APPLICATION 
PLENUM OPENING  FLOOR OPENING 
A  B  C  D 
14–3/16
*
(360) 
*. Not all families have these models
Upflow Applications on Combustible or Noncombustible Flooring 
(Subbase not required) 
12-11/16
(322) 
21-5/8
(549) 
13-5/16
(338) 
22-1/4
(565)
Downflow Applications on Noncombustible Flooring
(Subbase not required) 
12-9/16
(319) 
19
(483) 
13-3/16
(335) 
19-5/8
(498) 
Downflow applications on combustible flooring
(Subbase required) 
11-13/16
(284) 
19
(483) 
13-7/16
(341) 
20-5/8
(600) 
Downflow Applications on Combustible Flooring with coil assembly 
coil or coil box (Subbase not required) 
12-5/16
(319) 
19
(483) 
13-5/16
(338) 
20
(508)
17–1/2
(445) 
Upflow Applications on Combustible or Noncombustible Flooring 
(Subbase not required) 
16
(406)
21-5/8
(549)
16-5/8
(422) 
22-1/4
(565) 
Downflow Applications on Noncombustible Flooring
(Subbase not required) 
15-7/8
(403) 
19
(483) 
16-1/2
(419) 
19-5/8
(498) 
Downflow applications on combustible flooring
(Subbase required) 
15-1/8
(384) 
19
(483) 
16-3/4
(425) 
20-5/8
(600) 
Downflow Applications on Combustible Flooring with coil assembly 
coil or coil box (Subbase not required) 
15-1/2
(394) 
19
(483) 
16-1/2
(419) 
20
(508)
21
(533) 
Upflow Applications on Combustible or Noncombustible Flooring 
(Subbase not required) 
19-1/2
(495) 
21-5/8
(549) 
20-1/8
(511) 
22-1/4
(565) 
Downflow Applications on Noncombustible Flooring
 (Subbase not required) 
19-3/8
(492) 
19
(483) 
20
(508)
19-5/8
(498) 
Downflow applications on combustible flooring
 (Subbase required) 
18-5/8
(473) 
19
(483) 
20-1/4
(514) 
20-5/8
(600) 
Downflow Applications on Combustible Flooring with coil assembly 
coil or coil box (Subbase not required) 
19
(483)
19
(483) 
20
(508) 
20
(508)
24-1/2
(622) 
Upflow Applications on Combustible or Noncombustible Flooring 
(Subbase not required) 
23
(584) 
21-1/8
(537) 
23-5/8
(600) 
22-1/4
(565) 
Downflow Applications on Noncombustible Flooring 
(Subbase not required) 
22-7/8
(581) 
19
(483) 
23-1/2
(597) 
19-5/8
(498) 
Downflow applications on Combustible flooring
(Subbase required) 
22-1/8
(562) 
19
(483) 
23-3/4
(603) 
20-5/8
(600) 
Downflow Applications on Combustible Flooring with coil assembly 
coil or coil box (Subbase not required) 
22-1/2
(572) 
19
(483) 
23-1/2
(597) 
20
(508)