PG92MSA: Installation, Start-up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
8
AIR FOR COMBUSTION AND VENTILATION
Introduction
Direct Vent (2-pipe) Applications
When the furnace is installed as a direct vent (2-pipe) furnace, no special
provisions  for  air  for  combustion  are  required.  However,  other  gas
appliances installed in the space with the furnace may require outside air
for  combustion.  Follow  the  guidelines  below  to  ensure  that  other  gas
appliances have sufficient air for combustion.
Non-Direct Vent (1-pipe) Applications
When  the  furnace  is  installed  as  a  non-direct  vent  (1-pipe)  furnace,  it
will be necessary to ensure there is adequate air for combustion. Other
gas  appliances  installed  with  the  furnace  may  also  require  air  for
combustion and ventilation in addition to the amount of combustion air
and ventilation air required for the furnace. Follow the guidelines below
to ensure that the furnace and other gas appliances have sufficient air for
combustion.
Ventilated Combustion Air Applications (for U.S. Only)
When the furnace is installed using the ventilated combustion air option,
the  attic  or  crawlspace  must  freely  communicate  with  the  outdoor  to
provide sufficient air for combustion. The combustion air pipe cannot be
terminated in attics or crawlspaces that use ventilation fans designed to
operate during the heating season. If ventilation fans are present in these
areas, the combustion air pipe must terminate outdoors as a Direct Vent/
2-Pipe system.
All air for combustion is piped directly to the furnace from a space that is
well  ventilated  with  outdoor  air  (such  as  an  attic,  crawl  space  or
equipment closet) and the space is well isolated from the living space or
garage. In addition, other gas appliances installed in the space with the
furnace may require  outside air for combustion.  Follow the guidelines
below  to  ensure  that  the  roof  or  crawlspace  walls  have  sufficient  free
area  to  provide  sufficient  air  for  combustion  and  ventilation  for  the
furnaces.  The  guidelines  below  can  be  used  to  ensure  that  other  gas
appliances have sufficient air for combustion.
Provisions for adequate combustion, ventilation, and dilution air must be
provided in accordance with:
• U.S.A.  Installations:  Section  9.3  of  the  current  edition  of  NFPA
54/ANSI Z223.1, Air for Combustion and Ventilation and applicable
provisions of the local building codes.
CAUTION
!
PERSONAL INJURY AND/OR PROPERTY
DAMAGE HAZARD
Improper  use  or  installation  of  this  furnace  may  result  in  premature
furnace  component  failure.  Unless  otherwise  prohibited,  this  gas
furnace may be used for heating buildings under construction provided
that:
- The furnace is permanently installed with all electrical wiring,
piping,  venting  and  ducting  installed  according  to  these
installation instructions. A return air duct is provided, sealed to
the furnace casing, and terminated outside the space containing
the  furnace.  This  prevents  a  negative  pressure  condition  as
created  by  the  circulating  air  blower,  causing  a  flame  rollout
and/or drawing combustion products into the structure. 
- The  furnace  is controlled by  a thermostat. It  may  not  be  “hot
wired”  to  provide  heat  continuously  to  the  structure  without
thermostatic control. 
- Clean  outside  air  is  provided  for  combustion.  This  is  to
minimize the corrosive  effects  of  adhesives,  sealers  and  other
construction  materials.  It  also  prevents  the  entrainment  of
drywall dust into combustion air, which can cause fouling and
plugging of furnace components. 
- The  temperature of  the return air to  the  furnace is  maintained
between 55°F (13°C) and 80°F (27°C), with no evening setback
or shutdown. The use of the furnace while the structure is under
construction  is  deemed  to  be  intermittent  operation  per  our
installation instructions. 
- The  air  temperature  rise  is  within  the  rated  rise  range  on  the
furnace rating plate,  and the gas input rate has  been set to the
nameplate value. 
- The  filters  used  to  clean  the  circulating  air  during  the
construction  process  must  be  either  changed  or  thoroughly
cleaned prior to occupancy. 
- The  furnace,  ductwork  and  filters  are  cleaned  as  necessary  to
remove  drywall  dust  and  construction  debris  from  all  HVAC
system components after construction is completed. 
- Verify  proper  furnace  operating  conditions  including  ignition,
gas  input  rate,  air  temperature  rise,  and  venting  according  to
these installation instructions.
WARNING
!
CARBON MONOXIDE POISONING / COMPONENT 
DAMAGE HAZARD
Failure to follow this warning could result in personal injury or death
and unit component damage. 
Corrosive or contaminated air may cause failure of parts containing flue
gas, which could leak into the living space. Air for combustion must not
be  contaminated  by  halogen  compounds,  which  include  fluoride,
chloride,  bromide,  and  iodide.  These  elements  can  corrode  heat
exchangers  and  shorten  furnace  life.  Air  contaminants  are  found  in
aerosol  sprays,  detergents,  bleaches,  cleaning  solvents,  salts,  air
fresheners, and  other  household  products. Do  not  install  furnace in a
corrosive or contaminated atmosphere. Make sure all combustion and
circulating air requirements are met, in addition to all local codes and
ordinances.
CAUTION
!
FURNACE RELIABILITY HAZARD
Failure to follow this caution may result in nuisance limit switch 
cycling and unit component damage.
When a 17-1/2-in. wide upflow N coil is used with a 42060B furnace, 
the N coil must either be raised using a transition piece at least 3-in. (76 
mm) high or if a transition piece is not used, the refrigerant lines must 
point to the front of the furnace casing.
CAUTION
!
FURNACE CORROSION HAZARD
Failure to follow this caution may result in furnace damage. 
Air for combustion must not be contaminated by halogen compounds,
which include fluoride, chloride, bromide, and iodide. These elements
can corrode heat exchangers and shorten furnace life. Air contaminants
are  found  in  aerosol  sprays,  detergents,  bleaches,  cleaning  solvents,
salts, air fresheners, and other household products.