PG92MSA: Installation, Start-up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
13
CONDENSATE DRAIN CONNECTION
DO NOT trap the drain line in any other location than at the condensate
drain trap supplied with the furnace. If possible, DO NOT route the drain
line where it may freeze. The drain line must terminate at an inside drain
to prevent freezing of the condensate and possible property damage.
Special  precautions  MUST  be  made  if  installing  furnace  in  an  area
which may drop below 32° F (0° C). This can cause improper operation
or damage to the equipment. If the furnace environment has the potential
of  freezing,  the  drain  trap  and  drain  line  must  be  protected.  In  areas
where the temperature may be below 32° F (0° C), a Condensate Freeze
Protection kit is required. The  kit includes a condensate trap with  heat
pad  and  replaces  the  factory-installed  condensate  trap.  Refer  to  the
Accessory  section  of  the  Product  Data  for  current  kit  number.  A
self-regulating, shielded and waterproof heat tape rated at 3 to 6 watt per
foot (10 to 20 watt  per  meter) at 115 volt, 40°F (4°C) may be used to
provide freeze protection of the remaining condensate drain line. Wrap
the  drain  trap  and  drain  line  with  the  heat  tape  and  secure  with
appropriate  plastic  ties.  Follow  the  heat  tape  manufacturer’s
recommendations. Prime the trap before furnace operation.
The  condensate  drain  line  must  be  supported  and/or  secured  per  local
codes. Supports and clamps should be spaced to prevent the drain  line
from sagging or being dislocated from the furnace or termination point.
In the absence of local codes, consult the current edition of the National
Standard Plumbing Code, in the current edition of U.S. or the National
Plumbing Code of Canada in Canada. 
Upflow/Downflow Orientation
In the Upflow or Downflow orientation, the condensate trap is inside the
furnace  casing.  The  condensate  drain  must  be  routed  from  the  trap
through the furnace casing. The condensate drain can be routed through
the left  or right side of the casing. (The left or right side is  as you are
viewing/facing the furnace from the front.)
An indoor coil condensate drain or humidifier drain can be connected to
the external furnace condensate drain provided:
• The drains are not hard piped together, and
• There is an air gap at the point where the two drain lines meet or
• All condensate piping is at least 3/4-in. PVC and there is a relief tee at
the top of condensate drain piping as shown in Fig. 12.
NOTE: On narrower casings, it may be easier to remove the condensate
trap,  connect  the  drain  line  components  and  re-install  the  condensate
trap. Read the steps thoroughly to familiarize yourself with the required
steps.
For Right Side Condensate Drain:
1. Remove the 7/8-in. knock-out from the right side of the casing. See
Fig. 15 for suggested knockout removal technique.
2. Remove the pre-formed rubber drain elbow and two spring clamps
from the loose parts bag.
3. Slide a spring clamp 1-inch (25 mm) down the plain end (the end
without the formed grommet) of the drain elbow.
4. From inside the casing, insert the formed grommet end of the elbow
through the 7/8-in. knockout in the casing.
5. Pull  the  grommet  through  the  casing  from  the  outside  until  it  is
seated in the knockout
6. Attach  the  plain  end  of  the  drain  elbow to  the  outlet  stub  on  the
drain trap. Secure the drain elbow to the trap with the spring clamp.
A11342A
Fig. 14 – Formed Rubber Drain Grommet
NOTICE
!
The field-supplied, accessory horizontal drain trap grommet is ONLY
REQUIRED  FOR  DIRECT  VENT  APPLICATIONS.  It  it  NOT
required for applications using single-pipe or ventilated combustion air
venting.
NOTICE
!
The  condensate  trap  extends  below  the  side  of  the  casing  in  the
horizontal  position.  A  minimum  of  2-in.  (51  mm)  of  clearance  is
required between the casing side and the furnace platform for the trap to
extend out of the casing in the horizontal position. Allow at least 1/4-in.
per foot (20 mm per meter) of slope down.
CAUTION
!
FROZEN AND BURST WATER PIPE HAZARD
Failure  to  protect  against  the  risk  of  freezing  may  result  in  property
damage.
Special  precautions  MUST  be  made  if  installing  furnace  in  an  area
which may drop below freezing. This can cause improper operation or
damage  to  equipment.  If  furnace  environment  has  the  potential  of
freezing,  the  drain  trap  and  drain  line  must  be  protected.  The  use  of
accessory drain trap heaters, electric heat tape and/or RV antifreeze is
required for these installations. 
CAUTION
!
PROPERTY DAMAGE HAZARD
Failure  to  follow  this  caution  may  result  in  burst  water  pipes  and/or
property damage.
If a condensate pump is installed, a plugged condensate drain or a failed
pump  may  cause  the  furnace  to  shut  down.  Do  not  leave  the  home
unattended  during  freezing  weather  without  turning  off  water  supply
and  draining  water  pipes  or  otherwise  protecting  against  the  risk  of
frozen pipes.