PG92MSA: Installation, Start-up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
24
Refer to current edition of NSCNGPIC in Canada. After all connections
have been  made, purge lines and check  for leakage at furnace  prior to
operating furnace.
PRESSURE TESTING ABOVE ½ psig:
The furnace and it’s individual shut-off valve must be disconnected from
the gas supply piping system during any pressure testing of that system
at test pressures in excess of ½ psig (3.5 kPa).
PRESSURE TESTING BELOW ½ psig:
The furnace must be isolated from the gas supply piping by closing its
individual manual shut-off valve during any pressure testing of the gas
supply piping system at test pressures equal to or less than ½ psig (3.5
kPa).
An  accessible  manual  equipment  shutoff  valve  MUST  be  installed
external to furnace casing and within 6 ft. (2 M) of furnace. 
Install a sediment trap externally in the riser leading to furnace as shown
in Fig. 32. Connect a capped nipple into lower end of tee. Capped nipple
should extend below level of furnace gas controls. Place a ground joint
union between furnace gas control valve and exterior manual equipment
gas shutoff valve. 
A11035
Fig. 32 – Typical Gas Pipe Arrangement
A  1/8-in.  (3  mm)  NPT  plugged  tapping,  accessible  for  test  gauge
connection,  MUST  be  installed  immediately  upstream  of  gas  supply
connection  to  furnace  and  downstream  of  manual  equipment  shutoff
valve. 
Piping should be pressure and leak tested in accordance with the current
addition of the NFGC in the United States, local, and national plumbing
and gas codes before the  furnace has been  connected. Refer to current
edition of NSCNGPIC in Canada. After all connections have been made,
purge lines and check for leakage at furnace prior to operating furnace.
NOTE: The furnace gas control valve  inlet pressure  tap connection  is
suitable to  use as test gauge connection  providing test  pressure  DOES
NOT exceed maximum 0.5 psig (14-in. w.c.) stated on gas control valve.
See Fig. 65. 
If  pressure  exceeds  0.5  psig  (14-in.  w.c.),  gas  supply  pipe  must  be
disconnected  from  furnace  and  capped  before  and  during  supply  pipe
pressure test. If test pressure is equal to or less than 0.5 psig (14-in. w.c.),
turn off electric shutoff switch located on furnace gas control valve and
accessible  manual  equipment  shutoff  valve  before  and  during  supply
pipe pressure test. After all connections have been made, purge lines and
check for leakage at furnace prior to operating furnace. 
Gas Pipe Grommet
For direct vent (2-pipe) applications, the knockout for the gas pipe must
be  sealed  to  prevent  air  leakage.  Remove  the  knockout,  install  the
grommet  in  the  knockout,  then  insert  the  gas  pipe.  The  grommet  is
included in the loose parts bag. See Fig. 30.
ELECTRICAL CONNECTIONS 
See Fig. 33 for field wiring diagram showing typical field 115-V wiring.
Check all factory and field electrical connections for tightness. 
Field-supplied wiring shall conform with the limitations of 63°F (33_C)
rise. 
WARNING
!
FIRE OR EXPLOSION HAZARD
A failure to follow this warning could result in personal injury, death,
and/or property damage. 
If  local  codes  allow  the  use  of  a  flexible  gas  appliance  connector,
always use a new listed connector. Do not use a connector which has
previously  served  another  gas  appliance.  Black  iron  pipe  shall  be
installed at the furnace gas control valve and extend a minimum of 2-in.
(51 mm) outside the furnace.
GAS
SUPPLY
MANUAL
SHUT OFF
VALVE
(REQUIRED)
SEDIMENT
TRAP
UNION
NOTE:  Union may be inside the
vestibule where permitted by
local codes.
FRONT
WARNING
!
ELECTRICAL SHOCK, FIRE OR EXPLOSION HAZARD
Failure to follow safety warnings could result in dangerous operation,
serious injury, death or property damage.
Improper servicing could result in dangerous operation, serious injury,
death or property damage.
- Before servicing, disconnect all electrical power to furnace.
- When servicing controls, label all wires prior to disconnection.
Reconnect wires correctly.
- Verify proper operation after servicing.
- Always  reinstall  access  doors  after  completing  service  and
maintenance.
WARNING
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death. 
Blower  door  switch  opens  115-V  power  to  control.  No  component
operation can  occur. Do not bypass  or close  switch with  blower door
removed. 
WARNING
!
ELECTRICAL SHOCK AND FIRE HAZARD
Failure to follow this warning could result in personal injury, death, or
property damage. 
The  cabinet  MUST  have  an  uninterrupted  or  unbroken  ground
according  to  current  of  edition  NEC  NFPA  70  or  local  codes  to
minimize personal injury if an electrical fault should occur. In Canada,
refer  to  Canadian  Electrical  Code  CSA  C22.1.  This  may  consist  of
electrical  wire,  conduit  approved  for  electrical  ground  or  a  listed,
grounded power cord (where permitted by local code) when installed in
accordance  with  existing  electrical  codes.  Refer  to  the  power  cord
manufacturer’s ratings for proper wire gauge. Do not use gas piping as
an electrical ground.