PG92MSA: Installation, Start-up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
65
NOTE: After  cleaning, inspect the heat  exchangers to  ensure  they  are
free of all foreign objects that may restrict flow of combustion products.
8. Reverse items 6 through 1 for reassembly. 
9. Refer  to  furnace  wiring  diagram  and  reconnect  wires  to  flame
rollout switch, gas valve, igniter, and flame sensor.
10. Turn on gas and electrical supplies to furnace.
11. Check furnace operation through 2 complete heat operating cycles.
Look  at  burners.  Burner  flames  should  be  clear  blue,  almost
transparent. See Fig. 66.
12. Check for gas leaks. 
13. Replace main furnace door.
Secondary Heat Exchangers
The condensing side (inside) of the secondary heat exchanger CANNOT
be serviced or inspected without complete removal of the heat exchanger
assembly.  Detailed  information  on  heat  exchanger  removal  can  be
obtained from your Distributor.
WINTERIZATION
Since  the  furnace  uses  a  condensing  heat  exchanger,  some  water  will
accumulate in the unit as a result of the heat transfer process. Therefore,
once  it  has  been  operated,  it  cannot  be  turned  off  and  left  off  for  an
extended  period  of  time  when  temperatures  will  reach  32_F  (0_C)  or
lower  unless  winterized.  Follow  these  procedures  to  winterize  your
furnace:
1. Obtain  propylene  glycol  (RV/swimming  pool  antifreeze  or
equivalent).
2. Turn off gas and electrical supplies to your furnace.
3. Remove furnace control door.
4. Remove the top unused rubber plug from the port on the collector
box opposite the condensate trap. See Fig. 63.
5. Connect a field supplied 3/8-in. (9.5-mm) ID tube to the open port
on the collector box.
6. Insert a field supplied funnel into the tube.
7. Pour  one  quart  (liter)  of anti-freeze  solution  into  the  funnel/tube.
Antifreeze  should  run  through  the  inducer  housing,  overfill
condensate trap and flow to an open drain.
8. Replace the rubber plug in the port on the collector box.
9. Remove  the  middle  unused  rubber  plug  from  the  port  on  the
collector box opposite the condensate trap. See Fig. 63.
10. Repeat Steps 5 through 8.
11. If  a  condensate  pump  is  used,  check  with  pump  manufacturer  to
verify  pump  is  safe  for  use  with  antifreeze  used. Allow  pump  to
start and pump anti-freeze to open drain.
12. Replace main door.
13. When furnace is re-started, flush condensate pump with clear water
to check for proper operation before re-starting furnace.
14. Propylene glycol need not be removed before re-starting furnace.
SEQUENCE OF OPERATION
NOTE:  Furnace  control  must  be  grounded  for  proper  operation  or
control  will  lock  out.  Control  is  grounded  through  green/yellow  wire
routed  to  gas  valve  and  manifold  bracket  screw.  Using  the  schematic
diagram  in  Fig. 62,  follow  the  sequence  of  operation  through  the
different modes. Read and follow the wiring diagram very carefully.
NOTE:  If  a  power interruption occurs during a  call  for  heat (W),  the
control will start a 90-sec blower-only ON period two sec after power is
restored, if the thermostat is still calling for gas heating. The LED light
will flash code 12 and display will show (12.1) during the 90-sec period,
after  which  the  LED  will  be  ON  continuous,  as  long  as  no  faults  are
detected.  After  the  90-sec  period,  the  furnace  will  respond  to  the
thermostat normally. 
The blower door must be installed for power to be conducted through the
blower  door  interlock  switch  ILK  to  the  furnace  control  CPU,
transformer  TRAN,  inducer  motor  IDM,  blower  motor  BLWM,
hot-surface igniter HSI, and gas valve GV. 
1. Heating 
See Fig. 38 and Fig. 39 for thermostat connections. 
The  wall  thermostat  “calls  for  heat,”  closing  the  R-to-W  circuit.
The  furnace  control  performs  a  self-check,  verifies  the  pressure
switch contacts LPS and HPS are open, and starts the inducer motor
IDM. 
a. Inducer Prepurge Period- As the inducer motor IDM comes up 
to speed, the collector box pressure switch contacts LPS close, 24 
VAC power is supplied for a field installed humidifier at the 
HUM terminal and the control begins a 15-sec prepurge period. 
The inducer housing pressure switch contacts HPS are ignored 
until one minute after the gas valve closes. 
b. Igniter Warm-Up- At the end of the prepurge period, the 
Hot-Surface Igniter HSI is energized for a 17-sec igniter 
warm-up period. 
c. Trial-for-Ignition Sequence- When the igniter warm-up period 
is completed, the main gas valve relay contacts GVR close to 
energize the gas valve GV, the gas valve opens. The gas valve 
GV permits gas flow to the burners where it is ignited by the 
HSI. Five sec after the GVR closes, a 2-sec flame proving period 
begins. The HSI igniter will remain energized until the flame is 
sensed or until the 2-sec flame proving period begins.
d. Flame-Proving- When the burner flame is proved at the 
flame-proving sensor electrode FSE, the furnace control CPU 
begins the blower-ON delay period and continues to hold the gas 
valve GV open. If the burner flame is not proved within two sec, 
the control CPU will close the gas valve GV, and the control 
CPU will repeat the ignition sequence for up to three more 
Trials-For-Ignition before going to Ignition-Lockout. Lockout 
will be reset automatically after three hours or by momentarily 
interrupting 115 vac power to the furnace, or by interrupting 24 
vac power at SEC1 or SEC2 to the furnace control CPU (not at 
W, G, R, etc.).
If flame is proved when flame should not be present, the furnace 
control CPU will lock out of Gas-Heating mode and operate the 
inducer motor IDM until flame is no longer proved.
e. Blower-ON Delay- If the burner flame is proven, the blower 
motor is turned on at HEAT speed 25 sec after the gas valve GV 
is energized. 
CAUTION
!
UNIT AND PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in unit component or property
damage.
If the furnace is installed in an unconditioned space where the ambient
temperatures may be 32_ F (0_ C) or lower, freeze protection measures
must be taken to prevent minor property or product damage.
CAUTION
!
UNIT COMPONENT DAMAGE HAZARD
Failure to follow this caution may result in damage to the furnace and
other property damage.
Do  not  use  ethylene  glycol  (automotive  antifreeze  coolant  or
equivalent). Failure of plastic components may occur.