10
GT
erminal
This setup option selects desired operation when the R--G circuit
changes state on the furnace control board depending on setup.
S DISABLED (Default)
S FAN -- turns on fan to selected fan speed when G termi-
nal is energized. See Fig. 26.
S FAN SPEED -- select Low, Med, High for all zones
when G terminal is energized
S SHUTDOWN -- shuts off fan and equipment when initi-
ated. This function may be activated by a dry contact
from an external device such as a float switch or a relay.
User selects whether the contact is NC -- normally closed
(default) or NO -- normally open. User Interface displays
SYSTEM MALFUNCTION on screen and registers G
terminal shutdown event in Last 10 System Events. See
Fig. 27.
S GEN (generator input) -- d isplays GENERATOR MAL-
FUNCTION pop--up message when G is energized. This
function requires the addition of a Generator Self Test
Verifier (Part No. GSV200) which must be purchased
separately. Visit www.GeneratorVerifier.com for details
and ordering information. See Fig. 26.
R
G
FE Fan Coil or
Variable Speed Furnace
A07114
Fig. 26 -- G Input Wiring for Blower Operation or Generator
Malfunction with (--B) Infinityt Control
R
G
FE Fan Coil or
Variable Speed Furnace
A07115
Fig. 27 -- G Input Wiring for System Shutdown
with (--B) Infinityt Control (Contact type selectable;
Normally Closed (default) or Normally Open)
High Stage T
imer
Minimum amount of time low stage must operate before high stage
is activated. Ten to 60 minutes. 10 = default
A demand of 5_F/2.8_C or more will override the staging timer.
Off
Dela y
S 90 seconds
S 120 seconds (default)
S 150 seconds
S 180 seconds
Amount of time the blower will continue to run after heating has
shut off.
Setup -- Fan Coil
HP/AC Airflow:
S COMFORT (default) Cooling airflow is varied depend-
ing on humidity and temperature demand settings. This
selection enables the full dehumidify and comfort capa-
bilities of the system. When COMFORT is not selected,
the unit will not run reduced airflows for dehumidifica-
tion. Heat Pump airflow is varied depending on outdoor
temperature to maximize comfort.
S EFFICIENCY -- fixed airflow used to achieve specified
ratings -- no dehumidification airflow reduction. This is
nominally 350 CFM/ton, but will vary if a 2 -- stage out-
door unit is used.
S MAXIMUM -- 400 CFM/ton. No dehumidification air-
flow reduction.
Dehum
Airflow:
S NORMAL (factory default) -- When equipment is run-
ning to dehumidify, the airflow is allowed to adjust to a
minimum to satisfy the dehumidification call.
S HIGH -- Minimum airflow during the dehumidify mode
is increased to reduce duct and register sweating. Also
increases minimum airflow during normal cooling opera-
tion to reduce duct sweating.
Heater
Size:
S (choices dependent upon fan coil model)
This will show the heater size entered during the start--up process.
This value can be changed to another value (limited by the model
number of the fan coil). If the electric heater is self--identifying, this
value is not shown.
GT
erminal
This setup option selects desired operation when the R--G circuit
changes state on the furnace control board depending on setup.
S DISABLED (Default)
S FAN -- turns on fan to selected fan speed when G termi-
nal is energized. See Fig. 26.
S FAN SPEED -- select Low, Med, High for all zones
when G terminal is energized
S SHUTDOWN -- shuts off fan and equipment when initi-
ated. This function may be activated by a dry contact
from an external device such as a float switch or a relay.
User selects whether the contact is NC -- normally closed
(default) or NO -- normally open. User Interface displays
SYSTEM MALFUNCTION on screen and registers G
terminal shutdown event in Last 10 System Events. See
Fig. 27.
S GEN (generator input) -- d isplays GENERATOR MAL-
FUNCTION pop--up message when G is energized. This
function requires the addition of a Generator Self Test
Verifier (Part No. GSV200) which must be purchased
separately. Visit www.GeneratorVerifier.com for details
and ordering information. See Fig. 26.
CCUID01-- B