SYMPTOM: When controlling a residential heat
          pump, and asking for cooling, the heat  
          comes on.
CAUSE: Heat pump is not selected "on" in the
          Advanced Setup.
REMEDY: Select heat pump on during Advanced
          Setup programming.  Consult the Owner's
          Manual. 
TROUBLESHOOTING
Page 12
SYMPTOM: When calling for cooling, both
          the heat and cool come on.
CAUSE: The Advanced Setup is configured
          to control a heat pump, and the hvac
          the thermostat is controlling is a
          "conventional" (non heat pump)
          system.
REMEDY: Consult the Owner's Manual in 
          the Advanced Setup section to turn 
          off the heat pump.