APPENDIX B E CCN TABLES
All A Series units with (_l_?foFtLink TM controls have a port
for interface with the Carrier Comfort Network '_ (CCN)
system. On TB3 there is a Jll jack which can be used for
temporary connection to the CCN network or to computers
equipped with CCN software like the Service Tool. Also on
TB3 there are screw connections that can be used for more
permanent CCN connections.
In the following tables the structure of the tables which are
used with the Service Tool as well as the names and data that
are included in each table are shown. As a reference the equiv-
alent scrolling marquee tables and names are included. There
are several CCN variables that are not displayed through the
scrolling marquee and are used for more extensive diagnostics
and system evaluations.
STATUS DISPLAY TABLES
TABLE
COOLING
COOL_A
COOL_B
ECONDIAG
ECONOMZR
DISPLAY NAME
HVAC Mode .............. :
Control Mode ........... :
Current Running Capacity
Cooling Control Point
Evaporator Discharge Tmp
Mixed Air Temperature
Compressor A1 Relay
Compressor A1 Feedback
Compressor A1 Timeguard
Compressor A2 Relay
Compressor A2 Feedback
Compressor A2 Timeguard
Minimum Load Valve
Cir A Discharge Pressure
Cir A Suction Pressure
Cir A Sat.Condensing Tmp
Cir A Sat.Suction Temp.
Compressor B1 Relay
Compressor B1 Feedback
Compressor B1 Timeguard
Compressor B2 Relay
Compressor B2 Feedback
Compressor B2 Timeguard
Cir B Discharge Pressure
Cir B Suction Pressure
Cir B Sat.Condensing Tmp
Cir B Sat.Suction Temp.
Economizer Active ?
Conditions which prevent
economizer being active:
Econ Act. Unavailable?
Remote Econ. Disabled ?
DBC - OAT lockout?
DEW - OA Dewpt. lockout?
DDBC- OAT > RAT lockout?
OAEC- OA Enth Lockout?
DEC - Diff.Enth.Lockout?
EDT Sensor Bad ?
OAT Sensor Bad ?
Economizer forced ?
Supply Fan not on 30s ?
Cool Mode not in effect?
OAQ lockout in effect ?
Econ recovery hold off?
Economizer Act.Curr.Pos.
Economizer Act.Cmd.Pos.
Economizer Active ?
Economizer Control Point
Outside Air Temperature
Evaporator Discharge Tmp
Controlling Return Temp
RANGE
ascii text strings
ascii text strings
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
UNITS
%
dF
dF
dF
PSIG
PSIG
dF
dF
PSIG
PSIG
dF
dF
%
%
dF
dF
dF
dF
POINT NAME
CAPTOTAL
COOLCPNT
EDT
MAT
CMPA1
CSB A1
CMPA1 TG
CMPA2
CSB A2
CMPA2_TG
MLV
DPA
SP A
SCTA
SSTA
CMPB1
CSB B1
CMPB1 TG
CMPB2
CSB B2
CMPB2_TG
DPB
SP B
SCaB
SSTB
ECACTIVE
ECONUNAV
ECONDISA
DBC STAT
DEW STAT
DDBCSTAT
OAECSTAT
DEC STAT
EDT STAT
OAT STAT
ECONFORC
SFONSTAT
COOL OFF
OAQLOCKD
ECONHELD
ECONOPOS
ECONOCMD
ECACTIVE
ECONCPNT
OAT
EDT
RETURN_T
WRITE STATUS
forcible
forcible
forcible
148