TABLE
ECON MIN
EC_DIAG
APPENDIX B E CCN TABLES (cont)
MAINTENANCE DISPLAY TABLES (cont)
DISPLAY NAME
Econo Damper Command Pos
Econo Damper Current Pos
Econo Current Min. Pos.
Dill.Air Quality in PPM
Econo Position Override
IAQ Min.Pos.Override
Econ Remote 10K Pot Val.
IAQ - PPM Return C02
OAQ - PPM Return C02
IAQ - Discrete Input
IAQ Demand Vent Min.Pos.
Economizer Min.Position
IAQ Analog Sensor Config
IAQ 4-20 ma Fan Config
IAQ Discrete Input Confg
IAQ Disc.In. Fan Config
IAQ Econo Override Pos.
Dill.Air Quality LoLimit
Dill.Air Quality HiLimit
DAQ PPM Fan Off Setpoint
DAQ PPM Fan On Setpoint
Diff. AQ Responsiveness
IAQ Low Reference
IAQ High Reference
OAQ Lockout Value
OAQ 4-20ma Sensor Config
IAQ milliamps
OAQ milliamps
Economizer Active ?
Conditions which prevent
economizer being active:
Econ Act. Unavailable?
Remote Econ. Disabled ?
DBC - OAT lockout?
DEW - OA Dewpt. lockout?
DDBC- OAT > RAT lockout?
OAEC- OA Enth Lockout?
DEC - Diff.Enth.Lockout?
EDT Sensor Bad ?
OAT Sensor Bad ?
Economizer forced ?
Supply Fan not on 30s ?
Cool Mode not in effect?
OAQ lockout in effect ?
Econ recovery hold off?
Outside Air Temperature
OutsideAir DewPoint Temp
Outside Air ReI.Humidity
Outdoor Air Enthalpy
Return Air Temperature
Return Air ReI.Humidity
Return Air Enthalpy
High OAT Lockout Temp
Econ ChangeOver Select
OA Enthalpy ChgOvr Selct
Outdr.Enth Compare Value
OA Dewpoint Temp Limit
Supply Fan State
Economizer Act.Cmd.Pos.
Economizer Act.Curr.Pos.
Evaporator Discharge Tmp
Economizer Control Point
EDT Trend in degF/minute
Economizer Prop.Gain
Economizer Range Adjust
Economizer Speed Adjust
Economizer Deadband
Economizer Timer
RANGE UNITS
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
%
%
%
%
%
%
%
ma
ma
dF
dF
%
dF
%
dF
dF
%
%
dF
dF
^F
^F
^F
sec
POINT NAME
ECONOCMD
ECONOPOS
ECMINPOS
DAQ
ECOORIDE
IAQMINOV
ECON POT
IAQ
OAQ
IAQIN
IAQMINP
ECONOMIN
IAQANCFG
IAQANFAN
IAQINCFG
IAQINFAN
IAQOVPOS
DAQ LOW
DAQ HIGH
DAQFNOFF
DAQFNON
IAQREACT
IAQREFL
IAQREFH
OAQLOCK
OAQANCFG
IAQ MA
OAQMA
ECACTIVE
ECONUNAV
ECONDISA
DBC STAT
DEW- STAT
DDBCSTAT
OAECSTAT
DEC STAT
EDT STAT
OAT STAT
ECONFORC
SFONSTAT
COOL OFF
OAQLOCKD
ECONHELD
OAT
OADEWTMP
OARH
OAE
RAT
RARH
RAE
OAT LOCK
ECON SEL
OAEC SEL
OAEN CFG
OADE_/CFG
SFAN
ECONOCMD
ECONOPOS
EDT
ECONCPNT
EDTTREND
EC PGAIN
EC RANGE
EC SPEED
EC DBAND
ERATETMR
WRITE STATUS
forcible
forcible
forcible
forcible
forcible
forcible
forcible
config
config
config
config
config
config
config
config
config
config
config
config
config
config
config
config
forcible
forcible
forcible
forcible
config
config
config
config
config
forcible
config
config
config
config
config