ITEM EXPANSION RANGE DEFAULT ENTRY
-*AQ.S.R-*IQ.R.L IAQ Low Reference 0 - 5000 0
-,AQ.S.R-,IQ.R.H IAQ High Reference 0 - 5000 2000
-eAQ.S.R-eOQ.R.L OAQ Low Reference 0 - 5000 0
-,AQ.S.R-,OQ.R.H OAQ High Reference 0 - 5000 2000
-,IAQ.P IAQ PRE-OCCUPIED PURGE
-,IAQ.P-,IQ.PG IAQ Purge Yes/No No
-,IAQ.P-,IQ.P.T IAQ Purge Duration 5-60 min 15
-,IAQ.P-,IQ.P.L IAQ Purge LoTemp Min Pos 0-100 % 10
-,IAQ.P-,IQ.P.H IAQ Purge HiTemp Min Pos 0-100 % 35
-,IAQ.P-,IQ.L.O IAQ Purge OAT Lockout 35-70 dF 50
DEHU DEHUMIDIFICATION CONFIG.
-_D.SEL Dehumidification Config 0-2(multi-text strings) 0
-_D.SEN Dehumidification Sensor 1-2(multi-text strings) 1
-_D.EC.D Econ disable in DH mode? Yes/No Yes
-_D. VCF Vent Reheat Setpt Select 0-1 (multi-text strings) 0
-_D. VRA Vent Reheat RAT offset 0-8 AF 0
-_D. VHT Vent Reheat Setpoint 55-95 dF 70
-_D.C.SP Dehumidify Cool Setpoint 40-55 dF 45
-_D.RH.S Dehumidify RH Setpoint 10-90 % 55
CCN CCN CONFIGURATION
-,CCNA CCN Address 1 - 239 1
-,CCNB CCN Bus Number 0 - 239 0
-_BAUD CCN Baud Rate 1 - 5 (multi-text strings) 3
-_BROD CCN BROADCST DEFINITIONS
-_BROD-,TM.DT CCN Time/Date Broadcast ON/OFF On
-_BROD-,OAT.B CCN OAT Broadcast ON/OFF Off
-_BROD-,ORH.B CCN OARH Broadcast ON/OFF Off
-_BROD-,OAQ.B CCN OAQ Broadcast ON/OFF Off
-_BROD-,G.S.B Global Schedule Broadcst ON/OFF Off
-_BROD-,B.ACK CCN Broadcast Ack'er ON/OFF Off
-_SC.OV CCN SCHEDULES-OVERRIDES
-_SC.OV-eSCH.N Schedule Number 0 - 99 1
-_SC.OV-eHOL.T Accept Global Holidays? YES/NO No
-_SC.OV-eO.T.L. Override Time Limit 0 - 4 HRS 1
-_SC.OV-,OVEX Timed Override Hours 0 - 4 HRS 0
-_SC.OV-eSPT.O SPT Override Enabled ? YES/NO Yes
-_SC.OV-eT58.0 T58 Override Enabled ? YES/NO Yes
-_SC.OV-eGL.OV Global Sched. Override ? YES/NO No
ALLM ALERT LIMIT CONFIG.
-_SP.L.O SPT Io alert limit/occ -10-245 dF 60
-_SP.H.O SPT hi alert limit/occ -10-245 dF 85
-_SP.L.U SPT Io alert limit/unocc -10-245 dF 45
-_SP.H.U SPT hi alert limit/unocc -10-245 dF 100
-_SA.L.O EDT Io alert limit/occ -40-245 dF 40
-_SA.H.O EDT hi alert limit/occ -40-245 dF 100
-_SA.L.U EDT Io alert limit/unocc -40-245 dF 40
-_SA.H.U EDT hi alert limit/unocc -40-245 dF 100
-_RA.L.O RAT Io alert limit/occ -40-245 dF 60
-_RA.H.O RAT hi alert limit/occ -40-245 dF 90
-_RA.L.U RAT Io alert limit/unocc -40-245 dF 40
-_RA.H.U RAT hi alert limit/unocc -40-245 dF 100
-_R.RH.L RARH low alert limit 0-100 % 0
-_R.RH.H RARH high alert limit 0-100 % 100
-_SP.L SP low alert limit 0-5 "H20 0
-_SP.H SP high alert limit 0-5 "H20 2
-_BP.L BP Io alert limit -0.25-0.25 "H20 -0.25
-_BP.H BP high alert limit -0.25-0.25 "H20 0.25
-,IAQ.H IAQ high alert limit 0-5000 1200
TRIM SENSOR TRIM CONFIG.
-_SAT.T Air Temp Lvg SF Trim -10 - 10 AF 0
-_RAT.T RAT Trim -10 - 10 AF 0
-*OAT.T OAT Trim -10 - 10 AF 0
-_SPT.T SPT Trim -10 - 10 AF 0
-*CTA.T Cir A Sat.Cond.Temp Trim -30 - 30 AF 0
-*CTB.T Cir B Sat.Cond.Temp Trim -30 - 30 AF 0
-_SP.A.T Suct.Press.Circ.A Trim -50 - 50 PSIG 0
-_SP.B.T Suct.Press.Circ.B Trim -50 - 50 PSIG 0
-_DP.A.T Dis.Press.Circ.A Trim -50 - 50 PSIG 0
-_DP.B.T Dis.Press.Circ.B Trim -50 - 50 PSIG 0