CompensatedStartsectionformoreinformation.A setting of
0 minutes indicates Temperature Compensated Start in Cooling
is not permitted.
Temperature Compensated Start Heating Factor (T(_.H) --
This factor is used in the equation of the Temperature Compen-
sated Start Time Bias for heating. Refer to the Temperature
Compensated Start section for more information. A setting of
0 minutes indicates Temperature Compensated Start in Heating
is not permitted.
Fan Fail Shuts Downs Unit (SFS.S) -- This configuration
will determine whether the unit should shut down on a supply
fan status fail or simply alert the condition and continue to run.
If set to YES, then the control will shut down the unit and send
out an alarm if supply fan status monitoring fails. If set to NO,
the control will not shut down the unit if supply fan status mon-
itoring fails but the control will send out an alert.
Fan Status Monitoring (SFS.M) -- This configuration selects
the type of fan status monitoring to be performed.
0 - NONE -- No switch or monitoring
1 - SWITCH --Use of the fan status switch
2 - SP RISE -- Monitoring of the supply duct pressure.
VAV Unoccupied Fan Retry Time (VAES) -- Machine con-
trol types 1 and 2 (VAV-RAT, VAV-SPT) monitor the return-air
temperature during unoccupied periods to determine if there is
a valid demand for heating or cooling before initiating an unoc-
cupied heating or cooling mode. If the routine runs but con-
cludes a valid demand condition does not exist, then the pro-
cess is not permitted for the period of time defined by this con-
figuration. Reducing this value allows a more frequent re-
sampling process. Setting this value to zero will prevent any
sampling sequence.
Unit Size (SIZE) -- There are several unit sizes (tons) for the
A Series control. Make sure this configuration matches the size
called out by the model number of the unit. This is important as
the cooling stage tables are directly determined based on this
configuration.
Discharge Pressure Transducers (DRXR)-- This configuration
configures the unit for use with discharge pressure transducers.
The 48/50A2,A3,A4,A5 units will be automatically configured
for discharge pressure transducers and DRXR should be set to
Yes.
Suction Pressure Transducer Type (SRXR) -- This configu-
ration specifies the type of suction pressure transducer that is
being used. Set SRXR to 0 for support of a pressure transducer
with a range of 0 to 135 psig. Set SRXR to 1 for support of a
pressure transducer with a range of 0 to 200 psig.
NOTE: The 48/50A2,A3,A4,A5 units do not require a change
to the SRXR factory default setting.
Refrigerant Type (RFG 7")-- This configuration specifies the
type of refrigerant used in the unit. Configuration RFG T is set
to 0 if the refrigerant used is R-22. Configuration RFG T is set
to 1 if the refrigerant used is R-410A. Do not change this
setting.
Condenser Type (CND./3 -- This configuration specifies the
type of condenser installed in the unit. Configuration CND. T is
set to 0 if the condenser is a round tube, plate fin coil (RTPF).
Configuration CND. T is set to 1 if the condenser is a micro-
channel heat exchanger coil (MCHX).
MAT Calc Config (MAI:S) -- This configuration gives the
user three options in the processing of the mixed-air tempera-
ture (MAT) calculation:
• MAT.S = 0
There will be no MAT calculation.
• MA_S=I
The control will attempt to learn MAT over time. Any time
the system is in a vent mode and the economizer stays at a
particular position for long enough, MAT is set to equal
EDT. Using this, the control has an internal table whereby it
can more closely determine the true MAT value.
MAT.S = 2
The control will not attempt to learn MAT over time.
To calculate MAT linearly, the user should reset the MAT
table entries by setting MAT.R to YES. Then set MAT.S = 2.
The control will calculate MAT based on the position of the
economizer, outside-air temperature, and return-air
temperature.
To freeze the MAT table entries, let the unit run withMAr.S
= 1. Once sufficient data has been collected, change MAT.S
= 2. Do not reset the MAT table.
ITEM
UNIT
C.TYP
CVFN
RM.CF
CEM
TCS.C
TCS.H
SFS.S
SFS.M
VAVS
SIZE
DP.XR
SP.XR
RFG. T
CND. T
MAT.S
MAT.R
MAT.D
ALTI
DLAY
STAT
AUX.R
SENS
SPT.S
SP.O.S
SP.O.R
RRH.S
FLT.S
Table 43 -- Unit Configuration
EXPANSION
UNIT CONFIGURATION
Machine Control Type
Fan Mode (O=Auto, l=Cont)
Remote Switch Config
CEM Module Installed
Temp.Cmp.Strt.Cool Factr
Temp.Cmp.Strt.Heat Factr
Fan Fail Shuts Down Unit
Fan Stat Monitoring Type
VAV Unocc.Fan Retry Time
Unit Size (20-60)
Discharge Press. Transducers
Suct. Pres. Trans. Type
REFRIG: 0=R22, 1=R410A
CND HX TYP: O=RTPE I=MCHX
MAT Calc Config
Reset MAT Table Entries?
MAT Outside Air Default
Altitude ........ in feet:
Startup Delay Time
TSTAT-Both Heat and Cool
Auxiliary Relay Config
INPUT SENSOR CONFIG
Space Temp Sensor
Space Temp Offset Sensor
Space Temp Offset Range
Return Air RH Sensor
Filter Stat.Sw.Enabled ?
[ RANGE I UNITS [ CCN POINT I DEFAULTS
1-6
0-1
0-3
Yes/No
0 - 60
0 - 60
Yes/No
0-2
0 - 720
20 - 60
Yes/No
0-1
0-1
0-1
0-2
Yes/No
0-1O0
0 - 60000
0 - 900
Yes/No
0-3
Enable/Disable
Enable/Disable
1 -10
Enable/Disable
Enable/Disable
min
min
min
%
sec
CTRLTYPE
FAN MODE
RMT/NCFG
GEM BRD
TCSTCOOL
TCSTHEAT
SFS SHUT
SFS MON
SAMPMINS
UNITSIZE
DP TRANS
SPXRTYPE
REFRIG T
COILTYPE
MAT SEL
MATRESET
MATOADOS
ALTITUDE
DELAY
TSTATALL
AUXRELAY
SPTSENS
SPTOSENS
SPTO RNG
RARH-SENS
FLTS_ENA
4
1
0
No
0
0
No
0
50
20
No
0
Unit dependent
Unit dependent
1
No
20
0
0
No
0
Disable
Disable
5
Disable
Disable
36