Table 48 -- Cool/Heat Set Point Offsets Configuration
ITEM
D.LV.T
L.H.ON
H.H.ON
L.H.OF
L.C.ON
H.C.ON
L.C.OF
C.T.LV
H.T.LV
C.T.TM
H.T.TM
EXPANSION
COOL/HEAT SETPT. OFFSETS
Dmd Level Lo Heat On
Dmd Level(+) Hi Heat On
Dmd Level(-) Lo Heat Off
Dmd Level Lo Cool On
Dmd Level(+) Hi Cool On
Dmd Level(-) Lo Cool Off
Cool Trend Demand Level
Heat Trend Demand Level
Cool Trend Time
Heat Trend Time
[ RANGE 1 UNITS 1 CCN POINT J DEFAULT
-1 -2
0.5 - 20.0
0.5- 2
-1 -2
0.5 - 20.0
0.5- 2
0.1 -5
0.1 -5
30 - 600
30 - 600
AF
AF
AF
AF
AF
AF
AF
AF
sec
see
DMDLHON
DMDHHON
DMDLHOFF
DMDLCON
DMDHCON
DMDLCOFF
CTRENDLV
HTRENDLV
CTRENDTM
HTRENDTM
1.5
0.5
1
1.5
0.5
1
0.1
0.1
120
120
Timeguards -- In addition to the set points and offsets which
determine the trip points for bringing on and bringing off cool
modes there is a timeguard of 8 minutes which enforces a time
delay between the transitioning from a low cool to a high cool
mode. There is a timeguard of 5 minutes which enforces a thne
delay between the transitioning from a heat mode to a cool
mode.
Sz_ply Air Set Point (_ntrol -- Once the control has deter-
mined that a cooling mode is in effect, the cooling control
point (Run Status-+VIEW_(Z.C.P) is calculated and is
based upon either Setpoints-cSA.HI or Setpoints-cSA.LO,
depending on whether a high or a low cooling mode is in
effect, respectively. In addition, if supply air reset is config-
ured, it will also be added to the cooling control point.
Refer to the SumZ Cooling Algorithm section for a discus-
sion of how the A Series (_n_fortLink TM controls manage
supply-air temperature and the staging of compressors for these
control types.
Thermostat Cool Mode Selection ((2: TYP = 3 and 4) --
When a thermostat type is selected, the decision making pro-
cess involved in determining the mode is straightforward.
Upon energizing the Y1 input only, the unit HVAC mode will
be LOW COOL. Upon the energizing of both Y1 and Y2 in-
puts, the unit HVAC mode will be HIGH COOL. If just input
G is energized the unit HVAC mode will be VENT and the
supply fan will run.
Selecting the C TYP = 3 (TSTAT - MULTI) control type
will cause the control to do the following:
The control will read the Configuration-+UNIT--+SIZE
configuration parameter to determine the number of
cooling stages and the pattern for each stage.
An HVAC mode equal to LOW COOL will cause the
unit to select the Setpoints-cSA.LO set point to control
to. An HVAC mode equal to HIGH COOL will cause the
unit to select the Setpoints-cSA.HI set point to control
to. Supply air reset (if configured) will be added to either
the low or high cool set point.
The control will utilize the SumZ cooling algoritlnn and
control cooling to a supply air set point. See the section
for the SumZ Cooling Algorithm section for information
on controlling to a supply air set point and compressor
staging.
Selecting the C TYP = 4 (TSTAT - 2 STG) control type
means that only two stages of cooling will be used. On unit
sizes 020, 025 and 027 (with three compressors), an HVAC
Mode of LOW COOL will energize one compressor in Cir-
cuit A; an HVAC Mode of HIGH COOL will energize all
three compressors. On unit sizes 030 and larger (with four
compressors) an HVAC Mode of LOW COOL will energize
both compressors in Circuit A; an HVAC Mode of HIGH
COOL will energize all four compressors. Refer to the sec-
tion on Economizer Integration with Mechanical Cooling
for more information.
2-Stage Cooling Control Logic ((: TYP = 4 and 6) -- The
logic that stages mechanical cooling for the TSTAT and SPT
2-Stage cooling control types differs from that of the multi-
stage control types. This section will explain how compressors
are staged and the thning involved for both the Low Cool and
High Cool HVAC Modes.
There are either three or four compressors divided among two
refrigeration circuits. Circuit A always contains two compressors
(Outputs_COOL-cA1 and A2). Circuit B has either one com-
pressor (Outputs_,COOL-+B1) on size 020-027 units or two
compressors (Outputs_COOL-cB1 and B2) on size 030-060
units. For 2-stage cooling control, regardless of configuration,
there is no mmhnum load valve (MLV) control. The decision as
to which compressor should be mined on or offnext is decided
by the compressor's availability and the preferred staging order.
Either A1 or A2 may start first as there is a built-in lead/lag
logic on compressors A1 and A2 every time the unit stages to 0
compressors. Also, based on compressor availability, it should
be noted that any compressor may come on. For example, on a
3 compressor unit, if no compressors are currently on,
compressor A2 is currently under a minimum off compressor
timeguard, and 2 compressors are to be turned on, then com-
pressors A1 and B1 will be turned on hmnediately instead of
A1 and A2.
Low (_ol Vels'us High (_ol Mechanical Staging The num-
ber of compressors to be requested during a cooling mode are
divided into 2 groups by the control, HVAC mode = Lo Cool
and HVAC mode = Hi Cool.
If the economizer is not able to provide free cooling (Run
Status-+ECON--+ACTV = NO) then the following staging
occurs
Lo Cool Mode mechanical stages = 2
Hi Cool Mode mechanical stages = 3 (for 020 through 027
size units)
Hi Cool Mode mechanical stages = 4 (for 030 through 060
size units)
If the economizer is able to provide free cooling (Run Sta-
tus--+ECON---)ACTV = YES) then the following staging
occurs
1. If the economizer's current position is less than (bnfigu-
ration-cE(DN-cEC.MX- 5 and mechanical cooling
has not yet started for the current cool mode session then:
Lo Cool Mode mechanical stages = 0
Hi Cool Mode mechanical stages = 0
2. During the first 2.5 minutes of a low or high cool mode
where the economizer position is greater than (bnfigura-
tion --¢E(DN-cEC.MX- 5% and mechanical cooling
has not yet started:
Lo Cool Mode mechanical stages = 0
Hi Cool Mode mechanical stages = 0
3. If the economizer position is greater than (bnfiguration
--+ECON--+EC.MX- 5% for more than 2.5 minutes but
less than 5.5 minutes and mechanical cooling has not yet
started then:
4.
Lo Cool Mode mechanical stages = 1
Hi Cool Mode mechanical stages = 1
If the economizer position is greater than (bnfiguration
--+ECON--)ECMX- 5% for more than 5.5 minutes but
less than 8 minutes and mechanical cooling has started
42