ALARM OR
ALERT
NUMBER
A051
P051
T051
A052
P052
T052
A055
P055
T055
A056
P056
T056
T064
T065
T072
T073
T074
T075
T076
T078
T082
T090
T091
T092
T093
Tl10
Tlll
A120
P120
T120
A121
P121
T121
T122
T123
T126
T127
A140
A150
T153
A154
T155
A156
A157
A171
A172
A173
A174
T177
T178
A200
T210
T211
T220
T221
T229
Table 114 -- Alert and Alarm Codes
DESCRIPTION
Circuit A, Compressor 1 Stuck On Failure
Circuit A, Compressor 1 Failure
Circuit A, Compressor 1 Failure
Circuit A, Compressor 2 Stuck On Failure
Circuit A, Compressor 2 Failure
Circuit A, Compressor 2 Failure
Circuit B, Compressor 1 Stuck On Failure
Circuit B, Compressor 1 Failure
Circuit B, Compressor 1 Failure
Circuit B, Compressor 2 Stuck On Failure
Circuit B, Compressor 2 Failure
Circuit B, Compressor 2 Failure
Circuit A Saturated Condensing Thermistor Failure
(48/50AJ,AK,AW,AY units only)
Circuit B Saturated Condensing Thermistor Failure
(48/50AJ,AK,AW,AY units only)
Evaporator Discharge Reset Sensor Failure
Outside Air Temperature Thermistor Failure
Space Temperature Thermistor Failure
Return Air Thermistor Failure
Outside Air Relative Humidity Sensor Failure
Return Air Relative Humidity Sensor Failure
Space Temperature Offset Sensor Failure
Circuit A Discharge Pressure Transducer Failure
Circuit B Discharge Pressure Transducer Failure
Circuit A Suction Pressure Transducer Failure
Circuit B Suction Pressure Transducer Failure
Circuit A Loss of Charge
Circuit B Loss of Charge
Circuit A Low Saturated Suction Temperature Alarm.
Circuit A Low Saturated Suction Temp-Comp A2 Shutdown
Circuit A Low Saturated Suction Temperature Alert.
Circuit B Low Saturated Suction Temperature Alarm.
Circuit B Low Saturated Suction Temp-Comp B2 Shutdown
Circuit B Low Saturated Suction Temperature Alert.
ACTION TAKEN BY CONTROL
RESET PROBABLE CAUSE
METHOD
Turn off all compressors Manual
Automatic
Add strike to compressor (max 3)
Compressor locked off Manual
Turn off all compressors Manual
Automatic
Add strike to compressor (max 3)
Compressor locked off Manual
Turn off all compressors Manual
Automatic
Add strike to compressor (max 3)
Compressor locked off Manual
Turn off all compressors Manual
Automatic
Add strike to compressor (max 3)
Compressor locked off Manual
Use OAT for head pressure control
Welded contact
High pressure switch, compressor
current, wiring error
Exceeded 3 strike limit
Welded contact
High pressure switch, compressor
current, wiring error
Exceeded 3 strike limit
Welded contact
High pressure switch, compressor
current, wiring error
Exceeded 3 strike limit
Welded contact
High pressure switch, compressor
current, wiring error
Exceeded 3 strike limit
Automatic Faulty thermistor or wiring error
Use OAT for head pressure control Automatic
Unit shutdown Automatic
Stop use of economizer Automatic
Unit shutdown Automatic
Continue to run unit Automatic
Use OAT changeover control Automatic
Use differential dry bulb changeover Automatic
Use Space temperature without offset Automatic
Stop circuit Automatic
Stop circuit Automatic
Stop circuit Automatic
Stop circuit Automatic
Stop circuit Manual
Stop circuit Manual
Stop circuit Manual
Compressor A2 shutdown Automatic
Stop circuit Automatic
Stop circuit Manual
Compressor B2 shutdown Automatic
Circuit A High Saturated Suction Temperature
Circuit B High Saturated Suction Temperature
Circuit A High Head Pressure Stop
circuit Automatic
circuit Manual
circuit Manual
circuit Automatic
Stop
Stop
Stop
Stop circuit Automatic
Stop unit Manual
Stop unit Manual
Stop unit Manual
Stop unit Manual
Stop unit Manual
Stop unit Manual
Stop unit Manual
Stop gas heat Automatic
Stop options on CEM Automatic
Stop economizer & power exh Automatic
Stop unit Automatic
Stop demand limiting Automatic
Stop static pressure reset/VFD Automatic
Stop unit Manual
Close economizer, stop exhaust Automatic
Stop unit Automatic
Stop IAQ control Automatic
Use a default value for IAQ Automatic
Use software configured
minimum Automatic
Circuit B High Head Pressure
Reverse Rotation Detected
Unit is in Emergency Stop
Real Time Clock Hardware Failure
Serial EEPROM Hardware Failure
Serial EEPROM Storage Failure Error
Critical Serial EEPROM Storage Failure Error
A/D Hardware Failure
Staged Gas Control Board Comm Failure
Controls Expansion Module Comm Failure
ECB1 Board Communication Failure
ECB2 Board Communication Failure
4-20 MA Demand Limit Failure
4-20 MA Static Pressure ResetNFD Fail
Linkage Timeout Error - Communication Failure
Building Pressure Transducer Failure
Static Pressure Transducer Failure
Indoor Air Quality Sensor Failure
Outdoor Air Quality Sensor Failure
Economizer Minimum Position Override Input Failure
Faulty thermistor or wiring error
Faulty remote input on CEM board
Faulty thermistor or wiring error
Faulty thermistor or wiring error
Faulty thermistor or wiring error
Faulty sensor or wiring error
Faulty sensor or wiring error
Faulty sensor or wiring error
Faulty sensor, wiring error
Faulty sensor, wiring error
Faulty sensor, wiring error
Faulty sensor, wiring error
Low refrigerant charge
Low refrigerant charge
Low refrigerant charge, low airflow,
dirty coil, broken fan belt, TXV
problem
Low refrigerant charge, low airflow,
dirty coil, broken fan belt, TXV
problem
Low refrigerant charge, low airflow,
dirty coil, broken fan belt, TXV
problem
Low refrigerant charge, low airflow,
dirty coil, broken fan belt, TXV
problem
Low refrigerant charge, low airflow,
dirty coil, broken fan belt, TXV
problem
Low refrigerant charge, low airflow,
dirty coil, broken fan belt, TXV
problem
TXV problem, high load.
TXV problem, high load.
Dirty condenser, condenser fan
failure, system overcharged
Dirty condenser, condenser fan
failure, system overcharged
Incorrect compressor wiring
External shutdown command
Control Board failure, check lights
Control Board failure, check lights
Control Board failure, check lights
Control Board failure, check lights
Control Board failure, check lights
Control Board failure, check lights
Control Board failure, check lights
Control Board failure, check lights
Control Board failure, check lights
Input failure, wiring error
Input Failure, wiring error
Wiring errors, board failures
Sensor failure, wiring error
Sensor failure, wiring error
Sensor failure, wiring error
Sensor failure, wiring error
Input failure, wiring error