59
NOTE:  Some  parameters  in  the  menus  use  the  letters  MA  or
MAT, indicating a mixed air temperature sensor location before
the  cooling  coil.  This  unit  application  has  the  control  sensor
located after the cooling coil, in the fan section, where it is desig-
nated as (Cooling) Supply Air Temperature or SAT sensor.
SETUP AND CONFIGURATION
Before being placed into service, the W7220 Economizer module
must be set up and configured for the installed system.
The setup process uses a hierarchical menu structure that is easy to
use. Press the ▲ and ▼ arrow buttons to move forward and back-
ward through the menus and press the button to select and confirm
setup item changes.
Time-Out and Screensaver
When no buttons have been pressed for 10 minutes, the LCD dis-
plays a screen saver, which cycles through the Status items. Each
Status  item  displays  in  turn  and  cycles  to  the  next  item  after
5 seconds.
IMPORTANT: During setup, the economizer module is live at
all times.
Table 26 — W7220 Menu Structure* 
MENU PARAMETER
PARAMETER 
DEFAULT 
VALUE
PARAMETER 
RANGE AND 
INCREMENT
†
EXPANDED PARAMETER NAME
Notes
STATUS
ECON AVAIL NO YES/NO
FIRST STAGE COOLING DEMAND (Y1–IN)
YES = economizing available; the system can use outside air for 
free cooling when required
ECONOMIZING NO YES/NO
FIRST STAGE COOLING RELAY OUTPUT
YES = outside air being used for first stage cooling
OCCUPIED NO YES/NO
OCCUPIED
YES = OCC signal received from space thermostat or unitary 
controller
YES = 24 vac on terminal OCC
NO = 0 vac on terminal OCC
HEAT PUMP —**
COOL
HEAT
HEAT PUMP MODE
Displays COOL or HEAT when system is set to heat pump
(Non-conventional)
COOL Y1—IN OFF ON/OFF
FIRST STAGE COOLING DEMAND (Y1-IN)
Y1–I signal from space thermostat or unitary controller for cooling 
stage 1.
ON = 24 vac on terminal Y1–I
OFF = 0 vac on terminal Y1–I
COOL Y1—OUT OFF ON/OFF
FIRST STAGE COOLING RELAY OUTPUT
Cool stage 1 Relay Output to stage 1 mechanical cooling 
(Y1–OUT terminal)
COOL Y2—IN OFF ON/OFF
SECOND STAGE COOLING DEMAND (Y2–IN)
Y2–I signal from space thermostat or unitary controller for 
second stage cooling.
ON = 24 vac on terminal Y2–I
OFF = 0 vac on terminal Y2–I
COOL Y2—OUT OFF ON/OFF
SECOND STAGE COOLING RELAY OUTPUT
Cool Stage 2 Relay Output to mechanical cooling 
(Y2–OUT terminal)
MA TEMP
_ _ . _ °F
(or _ _ . _ °C)
–40°F to 150°F
(–40°C to 66°C)
SUPPLY AIR TEMPERATURE, Cooling Mode
Displays value of measured mixed air from MAT sensor.
Displays _ _ . _ F if not connected, short or out of range.
DA TEMP
_ _ . _ °F
(or _ _ . _ °C)
–40°F to 150°F
(–40°C to 66°C)
DISCHARGE AIR TEMPERATURE, after Heating section
Displays when Discharge Air Sylk Bus sensor is connected and 
displays measured discharge temperature.
Displays _ _ . _F if sensor sends invalid value, if not connected, 
short or out of range.
OA TEMP
_ _ . _ °F
(or _ _ . _ °C)
–40°F to 140°F
(–40°C to 60°C)
OUTSIDE AIR TEMP
Displays measured value of outdoor air temperature.
Displays _ _ . _F if sensor sends invalid value, short or out of 
range.
OA HUM _ _ % 0 to 100%
OUTSIDE AIR RELATIVE HUMIDITY
Displays measured value of outdoor humidity from OA Sylk Bus 
sensor.
Displays _ _% if not connected short, or out of range.
RA TEMP
_ _ . _ °F
(or _ _ . _ °C)
0°F to 140°F
(–18°C to 60°C)
RETURN AIR TEMPERATURE
Displays measured value of return air temperature from RAT 
Sylk Bus sensor.
Displays _ _ . _ F if sensor sends invalid value, if not connected, 
short or out of range
RA HUM _ _ % 0 to 100%
RETURN AIR RELATIVE HUMIDITY
Displays measured value of return air humidity from RA Sylk Bus 
sensor.
Displays _ _% if sensor sends invalid value, if not connected, 
short or out of range
IN CO2 _ _ _ ppm 0 to 2000 ppm
SPACE/RETURN AIR CO
2
Displays value of measured CO
2
 from CO
2
 sensor. Invalid if not 
connected, short or out of range. May be adjusted in Advanced 
menu by Zero offset and Span.