61
SETPOINTS 
(cont)
VENTMIN  2.25 V
2 to 10 vdc or 100 
to 9990 cfm 
increment by 10
DCV MINIMUM DAMPER POSITION
Displays only if a CO
2 
sensor is connected. Used for Va 
(ventilation min cfm) set point. This is the ventilation for less than 
maximum occupancy of the space.
100 to 9990 cfm; 
increment by 10
If OA, MA, RA, and CO
2
 sensors are connected and DCV CAL 
ENABLE is set to AUTO mode, the OA dampers are controlled 
by CFM and displays from 100 to 9990 CFM.
2 to 10 vdc
With 2-speed fan units VENTMIN L (low speed fan) and 
VENTMIN H (high speed fan) settings are required. Default for 
VENTMIN L is 2.5V and VENTMIN H is 2.25V
ERV OAT SP
††
32°F (0°C)
0°F to 50°F
(–18°C to 10°C);
increment by 
1 degree
ENERGY RECOVERY VENTILATOR UNIT OUTDOOR AIR 
TEMPERATURE SETPOINT
Only when AUX1 O = ERV
EXH1 SET 50%
0 to 100%;
increment by 1
EXHAUST FAN STAGE 1 SETPOINT
Set point for OA damper position when exhaust fan 1 is powered 
by the economizer.
With 2-speed fan units, Exh1 L (low speed fan) and Exh1 H (high 
speed fan) settings are required. Default for Exh1 L is 65% and 
Exh1 H is 50%
EXH2 SET 75%
0 to 100%;
increment by 1
EXHAUST FAN STAGE 2 SETPOINT
Set point for OA damper position when exhaust fan 2 is powered 
by the economizer. Only used when AUX1 O is set to EHX2.
With 2-speed fan units, Exh2 L (low speed fan) and Exh2 H (high 
speed fan) settings are required. Default for Exh2 L is 80% and 
Exh2 H is 75%
SYSTEM 
SETUP
INSTALL 01/01/10 —
Display order = MM/DD/YY
Setting order = DD, MM, then YY.
UNITS DEG °F °F or °C Sets economizer controller in degrees Fahrenheit or Celsius
EQUIPMENT CONV
CONV
or
HP
CONV = conventional; 
HP O/B = Enable Heat Pump mode. Use AUX2 I for Heat Pump 
input from thermostat or controller.
AUX2 IN W
Shutdown (SD)
Heat (W1)
HP(O)
HP(B)
In CONV mode:
SD = Enables configuration of shutdown (default);
W = Informs controller that system is in heating mode. 
NOTE: If using 2-speed fan mode, you must program CONV 
mode for W. Shutdown is not available in 2-speed fan mode.
In HP O/B mode: 
HP(O) = energize heat pump on Cool (default); 
HP(B) = energize heat pump on heat.
FAN SPEED 2 speed 1 speed/2 speed
Sets the economizer controller for operation of 1 speed or 2 
speed supply fan. The controller does not control the fan, but 
positions the OA and RA dampers to heating or cooling mode.
NOTE: 2-speed fan option also needs Heat (W1) programmed in 
AUX 2 In.
FAN CFM 5000 cfm
100 to 15000 cfm; 
increment by 100
UNIT DESIGN AIRFLOW (CFM)
Enter only if using DCVCAL ENA = AUTO
This is the capacity of the RTU. The value is found on the 
nameplate label for the specific unit.
AUX1 OUT NONE
NONE
ERV
EXH2
SYS
Select OUTPUT for AUX1 O relay
• NONE = not configured (output is not used)
• ERV = Energy Recovery Ventilator
††
• EXH2 = second damper position 24 vac out for second exhaust
  fan
• SYS = use output as an alarm signal
OCC INPUT INPUT or ALWAYS
OCCUPIED MODE BY EXTERNAL SIGNAL
When using a setback thermostat with occupancy out (24 vac), 
the 24 vac is input “INPUT” to the OCC terminal. If no occupancy 
output from the thermostat, then change program to “ALWAYS” 
OR add a jumper from terminal R to OCC terminal.
FACTORY DEFAULT NO NO or YES
Resets all set points to factory defaults when set to YES. LCD 
will 
briefly flash YES and change to NO but all parameters will 
change to the factory default values.
ADVANCED 
SETUP
MA LO SET 45
°
F (7°C)
35°F to 65°F
(2°C to 18°C); 
Increment by 1°F
SUPPLY AIR TEMPERATURE LOW LIMIT
Temperature to activate Freeze Protection (close damper or 
modulate to MIN POS if temp falls below set value).
FREEZE POS CLO CLO or MIN
FREEZE PROTECTION DAMPER POSITION
Damper position when freeze protection is active (closed or MIN 
POS).
CO2 ZERO 0ppm
0 to 500 ppm;        
Increment by 10
CO
2
 ppm level to match CO
2
 sensor start level.
CO2 SPAN 2000ppm
1000 to 3000 ppm; 
Increment by 50
CO
2
 ppm span to match CO
2
 sensor; e.g.: 500-1500 sensor 
output would be 500 CO
2
 zero and 1000 CO
2 
span.
Table 26 — W7220 Menu Structure* (cont)
MENU PARAMETER
PARAMETER 
DEFAULT 
VALUE
PARAMETER 
RANGE AND 
INCREMENT
†
EXPANDED PARAMETER NAME
Notes