86
Boldface indicates alternate standard static drive package is required.
Italics indicate  high static  drive  package with  different  motor pulley  is
required (all voltages).
Underscore
  indicates  operation  point  is  covered  by  factory  package.
Confirm max BHP based on unit voltage selected.
Table I — 48TCF*20 Vertical Supply (17.5 tons)
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
0.2 0.4 0.6 0.8 1.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
5250 547 1.10
626 1.45 700 1.84 766 2.24   828 2.67
5700 581 1.35
655 1.72 724 2.12 789 2.55   849 3.00
6150 615 1.63 684 2.02 750 2.44 812 2.90  871 3.37
6550 646 1.92 711 2.32 774 2.77 834 3.24  891 3.73
7000
682 2.28 743 2.71 803 3.17 860 3.66   915 4.17
7450 718 2.70 775 3.14 832 3.62 887 4.13  940 4.67
7900
755 3.16 809 3.62 863 4.12 915 4.65   966 5.21
8300
787 3.62 839 4.09 891 4.61 941 5.16   990 5.73
8750 825 4.18 874 4.68 923 5.22 971 5.78 1018 6.38
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
5250
  885 3.11   939 3.57   990 4.05 1038 4.54 1084 5.04
5700
  905 3.47   958 3.95 1008 4.45 1055 4.96 1100 5.48
6150  925 3.86   977 4.36 1026 4.88 1073 5.42 1118 5.96
6550
  945 4.24   995 4.76 1043 5.30 1090 5.86 1134 6.42
7000
  967 4.71 1017 5.26 1064 5.82 1109 6.39 1153 6.98
7450  991 5.22 1039 5.79 1085 6.38 1130 6.98 1172 7.59
7900
1015 5.78 1062 6.38 1107 6.99 1151 7.61 — —
8300 1038 6.33 1084 6.94 1128 7.57 1171 8.21 — —
8750 1064
6.99 1109 7.63 1152 8.28 — — — —
Standard static: 622-822 rpm, 3.7 max BHP
Medium static: 713-879 rpm
Voltage:    208v / 230v / 460v / 575v
Max BHP:  6.5  /  6.9  /  7.0  /  8.3
High static: 882-1078 rpm
Voltage:    208v / 230v / 460v / 575v
Max BHP:  6.5  /  6.9  /  7.0  /  8.3
High static drive with different motor pulley. Confirm max BHP 
coverage based on unit voltage selected.
APPENDIX C — FAN PERFORMANCE