201
MODETRIP
Unoccup. Cool Mode Start UCCLSTRT
Unoccup. Cool Mode End UCCL_END
Occupied Cool Mode Start OCCLSTRT
Occupied Cool Mode End OCCL_END
Ctl.Temp RAT,SPT or Zone CTRLTEMP
Occupied Heat Mode End OCHT_END
Occupied Heat Mode Start OCHTSTRT
Unoccup. Heat Mode End UCHT_END
Unoccup. Heat Mode Start UCHTSTRT
HVAC Mode…………..: ascii text strings string
TEMPCTRL
Evaporator Discharge Tmp dF EDT
Leaving Air Temperature dF LAT
Mixed Air Temperature dF MAT
Controlling Return Temp dF RETURN_T forcible
Controlling Space Temp dF SPACE_T forcible
TEMPS
Air Temp Lvg Supply Fan dF SAT
Return Air Temperature dF RAT forcible
Outside Air Temperature dF OAT forcible
Space Temperature dF SPT forcible
Space Temperature Offset ^F SPTO forcible
Staged Heat LAT Sum dF LAT_SGAS
Staged Heat LAT 1 dF LAT1SGAS
Staged Heat LAT 2 dF LAT2SGAS
Staged Heat LAT 3 dF LAT23SGAS
Staged Gas Limit Sw.Temp dF LIMSWTMP
Air Temp Lvg Evap Coil dF CCT
Cir A Sat.Condensing Tmp dF SCTA
Cir B Sat.Condensing Tmp dF SCTB
Cir A Sat.Suction Temp. dF SSTA
Cir B Sat.Suction Temp. dF SSTB
TSTAT
Control Mode………..: ascii text strings
Thermostat Y1 Input On/Off Y1 forcible
Thermostat Y2 Input On/Off Y2 forcible
Thermostat W1 Input On/Off W1 forcible
Thermostat W2 Input On/Off W2 forcible
Thermostat G Input On/Off G forcible
UINPUTS
Filter Status Input Dirty/Clean FLTS forcible
Fan request from IGC On/Off IGCFAN
Fire Shutdown Input Alarm/Normal FSD forcible
Thermostat G Input On/Off G forcible
Thermostat W2 Input On/Off W2 forcible
Thermostat W1 Input On/Off W1 forcible
Thermostat Y2 Input On/Off Y2 forcible
Thermostat Y1 Input On/Off Y1 forcible
Remote Input State On/Off RMTIN forcible
Enth. Switch Read High? Yes/No ENTH forcible
Supply Fan Status Switch On/Off SFS forcible
Circ A High Press.Switch On/Off CIRCAHPS
Circ B High Press.Switch On/Off CIRCBHPS
Freeze Status Switch Alarm/Normal FRZ forcible
Plenum Press.Safety Sw. High/Low PPS forcible
Demand Limit Switch 1 On/Off DMD_SW1 forcible
Demand Limit Switch 2 On/Off DMD_SW2 forcible
Pressurization Input Alarm/Normal PRES forcible
Evacuation Input Alarm/Normal EVAC forcible
Smoke Purge Input Alarm/Normal PURG forcible
IAQ - Discrete Input High/Low IAQIN forcible
Dehumidify Switch Input On/Off DHDISCIN forcible
UOUTPUTS
FANS
Supply Fan Relay On/Off SFAN
Supply Fan Commanded % 0 to 100 % SFAN_VFD
Supply Fan Request Yes/No SFANFORC forcible
Exhaust Fan Commanded % 0 to 100 % EFAN_VFD
Power Exhaust Relay 1 On/Off PE1
Power Exhaust Relay 2 On/Off PE2
Condenser Fan Output 1 On/Off CONDFAN1
Condenser Fan Output 2 On/Off CONDFAN2
Condenser Fan Output 3 On/Off CONDFAN3
Condenser Fan Output 4 On/Off CONDFAN4
APPENDIX B — CCN TABLES (CONT)
Table L — STATUS DISPLAY TABLES (cont)
TABLE DISPLAY NAME RANGE UNITS POINT NAME WRITE STATUS