205
APPENDIX B — CCN TABLES (CONT)
Table O — SERVICE-CONFIG TABLES (cont)
TABLE DISPLAY NAME RANGE UNITS POINT NAME DEFAULT
BP__
Building Press. Config 0 to 5 BLDG_CFG 0
Building Pressure Sensor Enable/Disable BPSENS Disable
Bldg. Press. (+/-) Range 0.10 to 0.25 "H2O BP_RANGE 0.25
Building Pressure Setp. –0.25 to 0.25 "H2O BPSP 0.05
BP Setpoint Offset 0 to 0.5 ^"H2O BPSO 0.05
Power Exhaust On Setp.1 0 to 100 % PES1 25
Power Exhaust On Setp.2 0 to 100 % PES2 75
VFD/Act. Fire Speed/Pos. 0 to 100 % BLDGPFSO 100
VFD/Act. Min. Speed/Pos. 0 to 100 % BLDGPMIN 10
VFD Maximum Speed 0 to 100 % BLDGPMAX 100
BP 1 Actuator Max Pos. 85 to 100 % BP1SETMX 100
BP 2 Actuator Max Pos. 85 to 100 % BP2SETMX 100
BP Hi Cap VFD Clamp Val. 5 to 25 % BLDGCLMP 10
Fan Track Learn Enable Yes/No DCFM_CFG NO
Fan Track Learn Rate 5-60 min DCFMRATE 15
Fan Track Initial DCFM –20000 to 20000 CFM DCFMSTRT 2000
Fan Track Max Clamp 0 to 20000 CFM DCFM_MAX 4000
Fan Track Max Correction 0 -20000 CFM DCFM_ADJ 1000
Fan Track Internl EEPROM –20000 to 20000 CFM DCFM_OFF 0
Fan Track Internal RAM –20000 to 20000 CFM DCFM_RAM 0
Fan Track Reset Internal Yes/No DCFMRSET No
Supply Air CFM Config 1 to 2 (multi-text strings) SCFM_CFG 1
Bldg.Pres.PID Run Rate 5 to 120 sec BPIDRATE 10
Bldg.Press. Prop. Gain 0 to 5 BLDGP_PG 1
Bldg.Press. Integ. Gain 0 to 2 BLDGP_IG 1
Bldg.Press. Deriv. Gain 0 to 5 BLDGP_DG 0.5
Prognostics BP Enable Disable/Enable PG_BP_EN
Prognostics BP Deadband "H2O PG_BP_DB
BP 1 Serial Number 1 0 to 9999 BP_1_SN1 0
BP 1 Serial Number 2 0 to 6 BP_1_SN2 0
BP 1 Serial Number 3 0 to 9999 BP_1_SN3 0
BP 1 Serial Number 4 0 to 254 BP_1_SN4 0
BP1 Cntrl Angle Lo Limit 0 to 90 BP1_CALM 35
BP 2 Serial Number 1 0 to 9999 BP_2_SN1 0
BP 2 Serial Number 2 0 to 6 BP_2_SN2 0
BP 2 Serial Number 3 0 to 9999 BP_2_SN3 0
BP 2 Serial Number 4 0 to 254 BP_2_SN4 0
BP2 Cntrl Angle Lo Limit 0 to 90 BP2_CALM 35
COOL
Enable Compressor A1 Enable/Disable CMPA1ENA Enable
Enable Compressor A2 Enable/Disable CMPA2ENA Enable
Enable Compressor A3 Enable/Disable CMPA3ENA Enable
Enable Compressor B1 Enable/Disable CMPB1ENA Enable
Enable Compressor B2 Enable/Disable CMPB2ENA Enable
Enable Compressor B3 Enable/Disable CMPB3ENA Enable
CSB A1 Feedback Alarm Enable/Disable CSB_A1EN Enable
CSB A2 Feedback Alarm Enable/Disable CSB_A2EN Enable
CSB A3 Feedback Alarm Enable/Disable CSB_A3EN Enable
CSB B1 Feedback Alarm Enable/Disable CSB_B1EN Enable
CSB B2 Feedback Alarm Enable/Disable CSB_B2EN Enable
CSB B3 Feedback Alarm Enable/Disable CSB_B3EN Enable
Capacity Threshold Adjst –10 to 10 Z_GAIN 1
Compressor Lockout Temp –25 to 55 dF OATLCOMP 53
Lead/Lag Configuration LEAD_LAG
Motor Master Control? Yes/No MOTRMAST No
Maximum Condenser Temp dF SCT_MAX
Minimum Condenser Temp dF SCT_MIN
A1 is a Digital Scroll Yes/No DIGCMPA1
A1 Min Digital Capacity % MINCAPA1
Dig Scroll Adjust Delta % DSADJPCT
Dig Scroll Adjust Delay sec DSADJDLY
Dig Scroll Reduce Delta % DSREDPCT
Dig Scroll Reduce Delay sec DSREDDLY
Dig Scroll Reduction OAT dF DSREDOAT
Dig Scroll Max Only OAT dF DSMAXOAT
Min Load Valve Enable Enable/Disable MLV_ENAB
Hi SST Alert Delay Time 5 to 30 min HSSTTIME 10
Rev Rotation Verified? Yes/No REVR_VER
Use CSBs for HPS Detect Yes/No CSbhpDET